71497?2615 • 0915 a.m. 10-20-2014 4114 <br /> REGEIVtD <br /> TAIT OCT 2 0 2014 <br /> 111 ENVIRONMENTAL HEALTH <br /> DEPARTMENT <br /> LEAK DETECTOR TESTING i <br /> =andas and Electric Company est Date: 9/18/2014EST LANE echnician : Victor Guerrero <br /> TONia 8017001-UTICC#: t <br /> Test Information s <br /> rLei*k <br /> Unleaded Diesel <br /> Gilbarco V-R Gilbarco V-R <br /> I <br /> Red Jacket Red Jacket j <br /> 1 <br /> ector(Yea/No) No Noi r 119295 100110491 ! <br /> i <br /> i Electronic LD(Y es/No) Yes Yes 3 <br /> j Calibrated Test Leak Rate: (189 Yes Yes j <br /> mil/min ® 10 PSI)(Yes/No) <br /> Check Valve Holding PSI 27 psi 31 psi j <br /> Resiliency (Bleed Back MIL) 55 MIL 35 MIL I <br /> i <br /> Slow Flow Metering PSI/(N/A) NA NA <br /> Turbine Shut Down Electronic LD Yes Yes 9 <br /> (Yes/No/NA) <br /> Slow Flaw At Novle NA NA <br /> (Yes/NO/NA) i <br /> Opening Time(Seconds) 3 Sec. 5 Sec. <br /> i <br /> Pass/Fail Pass Pass— <br /> This letter certifies that the annual leak detector tests were performed at the above referenced facility according to the <br /> l <br /> !i equipment manufacturers procedures and limitations and theresults as listed are to my knowledgetrue and correct The j <br /> leak detector test pass/fail is determined using a low Bow threshold trip rate of 3 gph at 10 PSI. <br /> i <br /> i <br /> (/ <br /> Technician Signature: `�� Date : 9/1812014 <br /> 4 <br />