SWRCB,January 2002 <br /> 6. PIPING SUMP TESTING <br /> Test Method Developed By: ❑Sump Manufacturer ❑X Industry Standard ❑Professional Engineer <br /> ❑Other(Specify) <br /> Test Method Used: ❑Pressure ❑Vacuum ❑Q Hydrostatic <br /> ❑Other(Specify) <br /> Test Equipment Used: Incon TS-STS Equipment Resolution: .0006 <br /> Unleaded Diesel Vent Sump Waste Oil <br /> Sump Diameter: 39" 38" 39" 32" <br /> Sump Depth: 36" 35" 36" 41" <br /> Sump Material: fiberglass fiberglass fiberglass Steel <br /> Height from Tank Top to Top of 14" 15" 14" 25" <br /> Highest Piping Penetration: <br /> Height from Tank Top to Lowest 23" 21" 21" n/a <br /> Electrical Penetration: <br /> Condition of sump prior to testing: good good good good <br /> Portion of Sump Tested' 2"above high pen 2"above high pen 2"above high pen 2"above high pen <br /> Does turbine shut down when Dyes ❑No ❑X NA <br /> sump sensor detects liquid(both ❑Yes❑No[ZINA ❑Yes❑No ❑X NA ❑Yes❑No ONA <br /> product and water)?* <br /> Turbine shutdown response time n/a n/a n/a n/a <br /> Is system programmed for fail-safe ❑Yes [—]No [Z]NA <br /> shutdown?* <br /> ❑Yes❑No❑Q NA ❑Yes❑No [ZINA ❑Yes[--]Nox❑NA <br /> Was fail-safe verified to be ❑Yes ❑No ❑X NA <br /> operational?* <br /> ❑Yes❑No ONA ❑Yes❑No [EINA ❑Yes❑No[KNA <br /> Wait time between applying <br /> pressure/vacuum/water and starting 15min 15min 15min 15min <br /> test: <br /> Test Start Time: 9:44am 10:OOam 9:44am 10:00 10:16 10:33 2:15 2:34 <br /> Initial Reading(R,): 3.8814 3.8810 4.0303 4.0301 4.5447 4.5446 5.6476 5.6473 <br /> Test End Time: 9:59am 10:15am 9:59am 10:15 10:32 10:48 2:30 2:49 <br /> Final Reading(RF): 3.8811 3.8810 4.0301 4.0300 4.5446 4.5443 5.6473 5.6473 <br /> Test Duration: 15min 15min 15min 15min 15min 15min 15min 15min <br /> Change in Reading(RF-R,): .0003 .0001 .0002 .0001 .0001 .0003 .0003 0 <br /> Pass/Fail Threshold or Criteria: .002 .002 .002 .002 .002 .002 .002 .002 <br /> Test Result: 0 Pass ❑Fail ❑X Pass ❑Fail ❑X Pass ❑Fail ❑X Pass ❑Fail <br /> Was sensor removed for testing? [E]Yes ❑No DNA [E]Yes❑No❑NA [E]Yes❑No DNA ❑X Yes❑No DNA <br /> Was sensor properly replaced and ❑Yes [E]No DNA <br /> verified functional after testing? ❑Yes❑X No❑NA ❑Yes[Z]No❑NA ❑Yes[Z]No❑NA <br /> Comments—(include information on repairs made prior to testing, and recommended_follow-up for failed tests) <br /> removed sensor for testing, put back after finish <br /> If the entire depth of the sump is not tested,specify how much was tested. If the answer to as of the questions indicated with an <br /> asterisk(*)is"NO"or"NA",the entire sump must be tested. (See SWRCB LG-160) <br />