Test Date: 12/06/2002 <br /> —OP <br /> , ogy Work Order. 2224654 <br /> SECONDARY CONTAINMENT TEST RESULTS <br /> SUMP TESTS <br /> Tank or Disp Manufacturer Model or Diam.NJidih2ength Depth Test Method Start Initial Level Finish Final Pass/ <br /> Type # Material {") ( ) Time Level Change Time Result Fail <br /> STP Sump SUP Trusco Fiberglass 32" 52" Hydrostatic-VPLT 0909 21" -.00017 0940 -.00273 Pass <br /> STP Sump REG Trusco Fiberglass 32" 51 Hydrostatic-VPLT 0821 20 .00004 0852 .00070Pass <br /> Dispenser Sump 1/2 Bravo Steel 18X24 11 Hydrostatic-VPLT 0958 2 -.250 0959 -.595 Fail <br /> Dispenser Sump 3/4 Bravo Steel 18X24 11 Hydrostatio-VPLT 1012 2 -.162 1019 -.386 Fail <br /> • <br /> Comments: <br />