Laserfiche WebLink
�-' SAN JOAQUIN COUNTY <br /> ENVIRONMENTAL HEALTH DEPARTMENT <br /> 600 East Main Street, Stockton, California 95202-3029 <br /> Telephone:(209)468-3420 Fax:(209)468-3433 Web:www sigov.orglehd/unitifl.htmi <br /> UNDERGROUND STORAGE TANK(UST) PROGRAM INSPECTION REPORT CONTINUED <br /> Faolky Facility 707 Yosemite Avenue, Manteca Inspection Oct 5, 2011 <br /> Address:Name; Quicki Kleen Address: <br /> Dale: <br /> VIOLATIONS <br /> HSC=CA Health and Safew Code;CFR=Code of Federal Regulatims <br /> # C1 C2 M Code Section C1=Class 1 violation;62=Class 2 violation;M=Minor violation <br /> On Site Records(continued) <br /> RCCRM2'30(d) <br /> CCR 2715(c) Designated operator monthly inspection:(1)alarms not documented;(24)spill containers,UDCs,and sumps <br /> if necessary)not inspected; 5 required test dates not checked or noted; 6 employee trainingnot verified <br /> CCR 2715(e) Designated operator monthly inspection reports not matMained on site for at least 12 months <br /> CCR 2715(Q Designated operator employee training:(1)not performed;(2)not current for at least one employee on site: <br /> 3 I not kept <br /> HSC 25281.5(b)(2) Unburied fuel piping at marinas not visually inspected at least dairy or log not kept <br /> observations <br /> HSC 25292.1 UST system is not operated to prevent unauthorized release,including spills and overfills <br /> HSC 25291(b) UST monitoring system incapable of detecting leak from primary containment into secondary containmempla <br /> CCR 2630(d) UST monitoring equipment is not installed or maintained to detect a leak at the earliest opportunity (M1) <br /> CCR 2632(c)(2) Monitoring system is not present in the interstitial space of a double walled UST (Mt) <br /> CCR 2638(f)(1) Failed to maintain a continuous monnoring system for underground piping&UDCs that activates an (#It) <br /> audible and visual alarm or sto flow of roduct al the dis nser when it detects a leak <br /> CCR 2631(a) Primary containment is not product tight <br /> HSC 25291(a)(2) Secondary containment for UST system is not tight <br /> CCR 2636(c)(1) All releases in secondary piping do not flow to a collection sump <br /> CCR 2636(a) Failed to have secondary containment for piping(includes conventional suction piping) (M2) <br /> HSC 25291(e) Water in 2-containment not removed,analyzed&properly disposed of <br /> CCR 2636(f)(2) Line leak delector(s)not installed or failed to detect a 3gallon per hour leak al 10 psi CCR 2635(b) No spill container or overfill prevention system installed IM21 <br /> 313 CCR 2635(b)(1) Spill container failed to contain a minimum capacity of five gallons,or failed to provide a means to keep (M2) <br /> the spill container em <br /> 314 CCR 2635(b)(2) Overfill prevention system was overridden or failed to meet overfill requirements IM2) <br /> 315 HSC 25299(f)(2) Tampering with or disabling leak detection devices or alarms <br /> 316 CCR 2631.1(a) UST system is not compatible with the substance stored <br /> 317 HSC 25298(a) Illegally abandoned UST system <br /> AB 1702(2903-2904) HSC 25290.1(installed between 07101103 and 06130/04) <br /> VPH System HSC 26290.1 installed on or after 07101104 <br /> Compatibility and permeability requirements:(a)UST system is not compatible with the substance stored;(b) <br /> 401 CCR 2631.1 results of the compatibility and permeability testing requirements listed in subsections CCR 2631(b)and(d) <br /> for a UST system installed after July 1,2004,were not submitted <br /> 402 HSC 252g0.1(c)(1) Primary containment not liquid or vapor tight <br /> HSC 25290.2 c 1 <br /> 403 HSC25290. <br /> H252W c2 1(c)(2) Secondary containmentcontainmentnot liquid or vapor tight <br /> SC <br /> 404 HSC 25290.1(c)(3) Secondm <br /> ary containment not constructed to prevent water intrusion <br /> HSC 25290.2(c)(3) <br /> 5290.2 c 3 <br /> 405 HSC 26290.1(d) Monitoring system not maintained to detect water intrusion into the secondary containment,or the entry of <br /> HSC 25290.2(d) liquid or vapor from the primary containment into the secondary containment <br /> 406 HSC 25290.1(e) Interstitial liquid measurement method,constant vacuum,or constant pressure in the interstitial space of the <br /> UST s tem not maintained <br /> HSC 25290.1 Q) UST system rest tested by one of the following methods prior to use:(1)Enhanced leak detection;(2)inert gas <br /> 407 <br /> HSC 25290.2 t ressure testa rovetl b SWRCB; 3 test method deemed equivalent to 1 or 2 by the SWRCB <br /> Emergency Generator Systems <br /> 501 CCR 2636(f)(6) Emergency generator monitoring system not checked daily or log not kept if no leak detector (Mt) <br /> 502 HSC 25281.5(b)(3) Unburied fuel piping not visually inspected at least monthly or log not kept Intl) <br /> UST9 in a Vault <br /> 601 HSC 25283.5(a)(1) All exterior surfaces of the tank and connected piping cannot be directly viewed <br /> 802 HSC 25283.5(a)(2) Structure that the UST is located in does not provide for secondary containment <br /> 603 HSC 25283.5(a)(3) Failed to conduct weekly UST inspections or maintain a log of weekly inspections <br /> 604 HSC 25283.5(a)(5) UST installed after July 1,2003,does not meet or exceed applicable sections of HSC 25291 <br /> Non-Pressurized Piping <br /> 701 CCR 2643(d) Daily monitoring of suction piping(pre-January 1,1984)not performed IM71 <br /> TMe: <br /> Muniappa Naidu (209) 468-3439 a. �r. d w'v—e'Z <br /> EFID23-02 Rev09101H1 Page UST INSPECTION REPORT <br />