Laserfiche WebLink
Vmi <br /> Vaporless Manufacturing, Inc. <br /> Quality Petroleum Equipment <br /> Solutions for Over 20 Years <br /> LDT- 890 Test Form &VMI Warranty Checklist <br /> ,' <br /> October 1 , 2006 <br /> Test Information: <br /> Date: 10-18-2010 Test Company: EPIC Compliance Systems LLC <br /> Telephone: 209-814-3726 Contact: Francene Escobar <br /> Site I.D: Ouicki Kleen Address: 707 E Yosemite Ave <br /> City: Manteca State: CA Zip: 95336 <br /> Type of Test Equipment: LDT-890 <br /> Submersible Pump Identification: <br /> MFG: Red Jacket Model No: Serial No: <br /> Leak Detector Identification: <br /> MFG: F.E Petro Model No: STP-MLD-D Serial No: 07091297 <br /> Replacement Leak Detector Identification: <br /> MFG: Model No: Serial No: <br /> Line Conditions <br /> 1. Type of Pipe: F.G 2. Diameter of Pipe: 2" 3. Length of Pipe: 70' <br /> 4. Burial Depth of Leak Detector: 24" 5. Kind of Fuel: Diesel 6. Date of Last Line Test: <br /> Test Conditions <br /> 1. Operating Pump Pressure: 30 2. Gallon per hour test rate: 3 @ 10 psi <br /> 3. Static Line Pressure (Pump Off): 29 4. Bleedback Test (Pump Off): 150 ml. <br /> 5. Step-through time to full flow 2 seconds (0 psi. to full pump pressure, no leak) <br /> 6. Leak detector stays in Leak Search Position with a 3 GPH leak -Yes: X PASS No: FAIL <br /> 7. Was the leak detector adjusted —Yes: No: X <br /> Symptoms <br /> 1. Won't find 3 GPH leak: 2. Stays in Slow Flow: <br /> 3. Other: <br /> ************ If This Unit Is Returned Under Warranty Please Complete The Following *********** <br /> Vaporless RGA#: Return By (Company): <br /> Telephone: Contact: <br /> Customer Control #: Address: <br /> City: State: Zip: <br /> (See Website -www.vaporiess.com - Technical Bulletin 032805) <br />