Laserfiche WebLink
Test Date: 7 Jun 1993 Work Order#: 961005 <br /> LEAK DETECTOR DATA <br /> Tank 1 Tank 2 Tank 3 Tank 4 Tank 5 Tank 6 <br /> Serial number: 1 2 3 <br /> Product: PREMIUM MIDGRADE UNLEADED <br /> Leak Detector <br /> manufacturer: REDJACKET REDJACKET REDJACKET <br /> Leak detector model: X.L.P X.L.P X.L.P <br /> Leak detector <br /> serial number: 110894447 202890955 107900522 <br /> Open time - sec: 3 3 3 <br /> Element holding-psi : 10 10 10 <br /> Resiliency - cc: 310 300 320 <br /> Leak calibration-cc: 252 252 252 <br /> Leak Rate - GPH: 4 . 00 4 . 00 4 .00 <br /> Metering PSI: 10 10 10 <br /> Detected Leak (Y/N) : YES YES YES <br /> Pass/Fail: PASS PASS PASS <br /> FAILED LEAK DETECTORS <br /> Tank 1 Tank 2 Tank 3 Tank 4 Tank 5 Tank 6 <br /> Leak Detector <br /> manufacturer: <br /> Leak detector model : <br /> Leak detector <br /> serial number: <br /> Leak Rate - GPH: <br /> Pass/Fail : <br /> LEAK DETECTOR TEST COMMENTS : <br /> NDE Eaviron rental Corporation-20000 Mariner Avenue Ste 500-Torrance,CA.90503-(310)5424342 Page 4 <br />