Laserfiche WebLink
INTEGRITY TANK TESTING SERVICES 41 West Yokuts Street <br /> (209) 474-1375 or "00) 262-8378 -tockton, Ca 95207 <br /> June 8, 1992 <br /> � � r1t <br /> Mr. Curly Lawrence APR Tel <br /> PANELLA TRUCKING INC. <br /> P. o. Box 5010 ENVIRONMENTAL HEALTH <br /> Stockton, California 95205 PERMIT/SERVICES <br /> Dear Mr. Lawrence; <br /> Following is a summary of the precision testing we recently <br /> conducted on the underground storage tank (s) at 5000 East Fremont <br /> Street . <br /> Enclosed are copies of the test worksheets, graphs, and/or computer <br /> summation for your submittal to the appropriate governmental agency. <br /> Individual computer generated readings will be forwarded as <br /> requested. <br /> A tank system may be considered tight, according to the current <br /> regulations if the the test results shown below do not exceed 0.05 <br /> gph. If the results are beyond this parameter, an unauthorized <br /> release may have occurred, and you should consider taking remedial <br /> action. <br /> TANK # OR TANK PRODUCT TEST WITHIN TIGHT <br /> LOCATION CAPACITY CONTAINED RESULTS TANK PARAMETERS <br /> East 10, 000 Gasoline -.008 Yes <br /> South 12, 000 Diesel Fuel +.000 Yes <br /> So. Middle 12,000 Diesel Fuel -.014 Yes <br /> No. Middle 12, 000 Diesel Fuel -.010 Yes <br /> North 12 , 000 Diesel Fuel +.035 Yes <br /> Please contact us if you need additional information or data . <br /> Sincerely, <br /> "���� <br /> W. N. Savage <br /> Certified Tester <br />