Laserfiche WebLink
INTEGRITY TANK TESTING SERVICES <br /> 41 WIST YOKUTS AVE. STOCKTON, CALIFORNIA 95207 " A gAA1' <br /> June 20, 1992 WNVIRONMENTAL HEALTH <br /> PERMIT/SERVICES <br /> Panella Trucking, Inc. Site: 5000 East Fremont <br /> Attention: Curly Lawrence Stockton, Ca. <br /> P. O. Bog 5010 <br /> Stockton, California 95205 <br /> Dear Mr. Lawrence; <br /> Following is a summary of the precision testing we recently conducted on <br /> your underground storage tank(s) at the above site. <br /> Enclosed are copies of the test worksheet, graphs, and/or computer <br /> generated summations for your submittal to the appropriate governmental <br /> agency. <br /> A tank system may be considered tight, according to the current regulations <br /> if the test results shown below do not exceed 0.05 gph. If the results are <br /> beyond this parameter, an unauthorized release may have occurred, and you <br /> should consider taking remedial action. <br /> TANK # OR TANK PRODUCT TEST WITHIN TIGHT <br /> LOCATION CAPACITY CONTAINED RESULTS TANK PARAMETERS <br /> West 7,500 Delo Motor Oil .0171 Yes <br /> Please contact us if you need additional information or assistance. <br /> Sincerely, <br /> W. N. Savage <br /> Certified Tester <br /> Stockton (209) 474-1375 Toll Free (800) 262-8378 Fax (209) 478-2454 <br />