Laserfiche WebLink
Integrity Tank Testing Systems, Inc. <br /> I T T S <br /> May 29, 1991 APR 2 3 12S <br /> ZNVIRANMENTAL HEALTH <br /> Mr. Curly Lawrence PERMIT/SERVICES <br /> Panella Trucking, Inc . <br /> P. O. Box 5010 <br /> Stockton, California 95205 �. <br /> Site: 5000 East Fremont Street <br /> Stockton, California <br /> Dear Mr. Lawrence: <br /> Following is a summary of the precision testing we recently <br /> conducted on your underground storage tank. <br /> Enclosed are copies of the test worksheets, graphs, and/or <br /> computer summation for your submittal to the appropriate <br /> governmental agency. Individual computer generated readings <br /> will be forwarded as requested. <br /> A tank system may be considered tight, according to the <br /> current regulations if the the test results shown below do <br /> not exceed 0 ,05 gph, If the results are beyond this <br /> parameter, an unauthorized release may have occurred, and <br /> you should consider taking remedial action. <br /> TANK # OR TANK PRODUCT TEST WITHIN TIGHT <br /> LOCATION CAPACITY CONTAINED RESULTS TANK PARAMETERS <br /> West 10, 000 Prem U/L +, 024 Yes <br /> Please contact us if you need additional assistance or <br /> information. <br /> SincLy, <br /> `tiI 11� <br /> W. N. Savage <br /> Certified Tester <br /> 800 262-8378 166 Frank West Circle Stockton, CA 95206 (209) 466-8036 <br />