Laserfiche WebLink
IT T S Integrity Tank Testing Systems, Inc, <br /> ENVIRONMILN IAL HEALTH <br /> April 5, 1991 PERMIT/SERVICES <br /> Panella Trucking, Inc, <br /> Atten: Curly Lawrence <br /> P. 0. Box 5010 <br /> Stockton, California 95205 <br /> Dear Mr. Lawrence; <br /> Following is a summary of the precision testing we recently <br /> conducted on your underground storage tank. <br /> Enclosed are copies of the test worksheets, graphs, and/or <br /> computer summation for your submittal to the appropriate <br /> governmental agency. Individual computer generated readings <br /> will be forwarded as requested. <br /> A tank system may be considered tight, according to the <br /> current regulations if the the test results shown below do <br /> not exceed 0 .05 gph, If the results are beyond this <br /> parameter, an unauthorized release may have occurred, and <br /> you should consider taking remedial action. <br /> TANK # OR TANK PRODUCT TEST WITHIN TIGHT <br /> LOCATION CAPACITY CONTAINED RESULTS TANK PARAMETERS <br /> North 12, 000 Manifolded Yes <br /> 12, 000 Diesel Fuel +,006 Yes <br /> South 12 , 000 Manifolded Yes <br /> 12 , 000 Diesel Fuel - ,018 Yes <br /> Fresh Oil 7 , 500 Delo Motor +,0293 Yes <br /> Please contact us if you need additional assistance or <br /> information. <br /> Sincerely, <br /> w- �_ <br /> W. N. Savage <br /> Certified Tester <br /> 800 262-8378 166 Frank West Circle Stockton, CA 95206 (209) 466-8036 <br />