Laserfiche WebLink
ITIS - Integrity Tank Testing SysterrIM, Inc. <br /> � . <br /> May 14 , 1990 <br /> Mr. Curly Lawrence <br /> Panella Trucking, Inc. <br /> P. O. Box 5010 Site: 5000 East Fremont <br /> Stockton, California 95205 Stockton, California <br /> Dear Mr. Lawrence: <br /> Following is a summary of the precision testing we <br /> recently conducted on your underground storage tank (s) . <br /> Enclosed are copies of the test worksheets and computer <br /> generated data for your submittal to the appropriate <br /> governmental agency. <br /> A tank system may be considered tight, according to the <br /> current regulations if the the test results shown below do <br /> not exceed 0.05 gph. If the results are beyond this <br /> parameter, an unauthorized release may have occurred, and <br /> you should consider taking remedial action. <br /> TANK # OR TANK PRODUCT TEST WITHIN TIGHT <br /> LOCATION CAPACITY CONTAINED RESULTS TANK PARAMETERS <br /> North 12, 000 Diesel -.0292 Yes <br /> 12, 000 <br /> Manifolded <br /> South 12 , 000 Diesel +,0144 Yes <br /> 12, 000 <br /> Manifolded <br /> West 10, 000 Prem U/L +.024 Yes <br /> Please contact us if you need additional assistance or <br /> information. <br /> Sincerely, <br /> ����2e <br /> ank KeCertifieer <br /> 800 262-8378 166 Fronk West Circle Stockton, CA 95206 (209) 466-8036 <br />