Laserfiche WebLink
IT T S Integrity Tank Testing Systems, Inc. <br /> TEST DATA AND <br /> TEST RESULTS <br /> April 4, 1988 <br /> .PANELLA TRUCKING, INC. <br /> P. 0. Box 5010 <br /> Stockton, California 95205 <br /> Site: 5000 East Fremont Street <br /> Stockton, California <br /> Following is a summary of the precision testing we recently <br /> conducted on your underground storage tank(s) . <br /> Enclosed are copies of the test worksheets and graphs gene- <br /> rated for your submittal to the appropriate governmental agency. <br /> A tank system is considered tight , according to the current <br /> rules , if the gain is less than . 02 or the loss is less than . 05 <br /> gallons per one hour of testing. If the results are beyond these <br /> parameters , you should consider taking some remedial action. <br /> TANK #/ TANK PRODUCT TEST WITHIN TIGHT <br /> LOCATION CAPACITY CONTAINED RESULTS TANK PARAMETERS <br /> Northwest 2, 000 Waste Oil -. 02808 yes <br /> Please contact us if you need additional assistance or <br /> information. <br /> Sincerely , <br /> Frank Kea r h <br /> Certified T ter <br /> 800 262-8378 166 Fronk West Circle Stockton, CA 95206 (209) 466-8036 <br />