IT T S Integrity Tank Testing Systems, Inc. <br /> TEST DATA AND <br /> TEST RESULTS <br /> May 7, 1988 <br /> Panella Trucking, Inc. <br /> Attn: Curly Lawrence <br /> P. 0. Box 5010 Site: 5000 Fast Fremont Street <br /> Stockton, California 95205 Stockton, California <br /> Dear Mr. Lawrence: <br /> Following is a summary of the precision testing we recently <br /> conducted on your underground storage tank(s) . <br /> Enclosed are copies of the test worksheets and graphs gene- <br /> rated for your submittal to the appropriate governmental agency. <br /> A tank system is considered tight , according to the current <br /> rules , if the gain is less than . 02 or the loss is less than . 05 <br /> gallons per one hour of testing. If the results are beyond these <br /> parameters , you should consider taking some remedial action. <br /> TANK /i/ TANK PRODUCT TEST WITHIN TIGHT <br /> LOCATION CAPACITY CONTAINED RESULTS TANK PARAMETERS <br /> West of <br /> Dispatch 7,, 500 Motor Oil -. 018896 Yes <br /> 10, 000 Prem U/L Gas -. 0077 Yes <br /> Please contact us if you need additional assistance or <br /> information. <br /> Sincerely, <br /> W. Savage <br /> Certified Tester <br /> 800 262-8378 166 Frank West Circle Stockton, CA 95206 (209) 466-8036 <br />