Laserfiche WebLink
INTE,n'RITY TANK TESTING SE"ICES <br /> P. 0. BOX 691736, STOCKTON, CA. �Q5269 <br /> ���° hL HEALTH <br /> " UEP,VC1 <br /> June 3, 1993 93 JU�122) PM 2: 03 <br /> Mr. Curly Lawrence <br /> Panella Trucking Inc. <br /> P. O. Box 5010 <br /> Stockton, Ca. 95205 <br /> Dear Mr. Lawrence; <br /> Following is a summary of the precision testing we recently conducted on your <br /> underground storage tanks. <br /> Enclosed are copies of the test worksheet, graphs, and/or computer generated <br /> summations for your submittal to the appropriate governmental agency. <br /> A tank system may be considered tight, according to the current regulations if the test <br /> results shown below do not exceed 0.05 gph. If the results are beyond this parameter, <br /> an unauthorized release may have occurred, and you should consider taking remedial <br /> action. <br /> TANK # OR TANK PRODUCT TEST WITHIN TIGHT <br /> LOCATION CAPACITY CONTAINED RESULTS PARAMETER <br /> West of Tower 10,000 Gasoline +.019 Yes <br /> North 12,000 Diesel Fuel -.032 Yes <br /> North Center 12,000 Diesel Fuel +.029 Yes <br /> South Center 12,000 Diesel Fuel -.0297 Yes <br /> South 12,000 Diesel Fuel +.033 Yes <br /> Please advise if you needed additional assistance or information <br /> Sincerely, <br /> 13ZU Sava" <br /> W. N. Savage <br /> Certified Tester <br /> STOCKTON (209) 474-1375 TOLL FREE (800) 262-8378 <br />