7. UNDEF ' ISPENSER CONTAINMETING T <br /> dNT (UDC ofessional Engineer <br /> Test Method Developed By: [QDC Manufacturer ® try <br /> Standard— <br /> ❑ Other(Specify) <br /> Test Method Used: ❑ <br /> Pressure ❑ Vacuum ®Hydrostatic <br /> ❑ Other(Specify) <br /> Test�1m Equipment Resolution: +/-0.002" <br /> Cut Used: Incon TS-STS Sump Test System <br /> C# 1/2 UDC# 3/4 UDC# UDC# <br /> UDC Manufacturer: <br /> UDC Material: Plastic Plastic <br /> UDC Depth: <br /> 30" 30" - — <br /> Height from UDC Bottom to Top 8„ 8" <br /> of Hi est Pi in Penetration: <br /> Height from UDC Bottom to 5" 5" DEC 14 2015 <br /> Lowest Electrical Penetration: <br /> Condition of UDC prior to Fair Fair F <br /> testis <br /> Portion of UDC Tested 4"Above Pen. 4" Above Pen. N pITV nCO�OT �C�IT <br /> Does turbine shut down when <br /> UDC sensor detects liquid(both ❑Yes❑No U NA ❑Yes❑No U NA ❑Yes❑No U NA ❑Yes❑No U NA <br /> product and water)? <br /> Turbine shutdown response time N/A N/A <br /> Is system programmed for fail- ❑Yes❑ No U NA ❑ Yes❑ No U NA ❑Yes❑No U NA ❑Yes❑ No E NA <br /> safe shutdown? <br /> Was fail-safe verified to be ❑Yes❑No U NA ❑Yes❑ No ®NA ❑ Yes ❑No ®NA ❑Yes❑No U NA <br /> operational? <br /> Wait time between applying <br /> pressure/vacuum/water and 30 minutes 30 minutes <br /> starung test <br /> Test Start Time: 10:01 AM 10:01 AM <br /> Initial Reading(R): 1.5049 5.3724 <br /> Test End Time: 10:16 AM 10:16 AM <br /> Final Reading(RF): 1.4472 5.3732 <br /> Test Duration: 15 min. 15 min. <br /> Change in Reading(RF-P): -0.0577 0.0008 <br /> Pass/Fail Threshold or Criteria: +/-0.002 +/-0.002 <br /> Test Result: Fail Pass <br /> Was sensor removed for testing? Yes Yes <br /> Was sensor properly replaced and <br /> verified functional after testing? I Yes Yes <br /> Comments— (include information on repairs made prior to test ng, and recommended follow-up for failed tests) <br /> Sensor functionality was not confirmed.This procedure is not part of the Secondary Containment Testing scope of work. <br /> If the entire depth of the UDC is not tested, specify how much was tested. If the answer to any of the questions indicated with an <br /> asterisk(s)is"NO"or"NA",the entire UDC must be tested. (See SWRCB LG-160) <br />