law J <br /> TEST DATE: 02/20/99 <br /> INVOICE #JB000362 AFFORDA-TE$T <br /> POB 36 - 26515 N SACRAMENTO BL <br /> THORNTON, CA 95686-0036 <br /> ( 209)794-0102 FAX ( 209)794-0112 <br /> TANK STATUS EVALUATION REPORT <br /> ----------------------------- <br /> ***** CUSTOMER DATA ***** ***** SITE DATA ***** <br /> STKN. SVC. STA. EQPT. CO. , INC. FAST <br /> W& EASY <br /> ARDIMART <br /> P.O.BOX 508 <br /> NG WAY <br /> 808 N. UNION ST. @ MONROE ST. <br /> STOCKTON, CA. STOCKTON, CA. <br /> 95201 95204 <br /> CONTACT: CORNELL, JIM CONTACT: KHAN, KHALID M. <br /> PHONE # : (209)464-8333 PHONE # : ( 209)948-8001 <br /> ***** COMMENT LINES ***** <br /> TWO DWFRP TANKS - PRESSURE SYSTEM - BALANCED VR <br /> OMTEC OEL8000 - ATG <br /> CURRENT EPA STANDARDS DICTATE THAT FOR UNDERGROUND FUEL TANKS, THE <br /> THE MAXIMUM ALLOWABLE HOURLY LEAK/GAIN RATE IS . 05 GALLONS. <br /> ULLAGE TESTS ARE ON A PASS/FAIL BASIS ONLY. <br /> TANK #1: REG UNLEADED TYPE: E-GLASS RATE: .001050 G.P.H. GAIN <br /> ULLAGE: PASS SIGNAL/NOISE: -. 03 <br /> TANK IS TIGHT. <br /> TANK #2: SUPER UNLEADED TYPE: E-GLASS RATE: .030427 G.P.H. GAIN <br /> ULLAGE: PASS SIGNAL/NOISE: -.05 <br /> TANK IS TIGHT. <br /> EQUIPMENT: USTEST <br /> OTTL# 97-1143 <br /> OPERATOR: LYLE D. NIMMO SIGNATURE: <br />