Laserfiche WebLink
0 <br /> Vertical Mounting Procedure Preparation <br /> Vertical Mounting Procedure <br /> AWARNING <br /> Ov <br /> This product is to be installed in systems operating near locations <br /> where highly combustible fuels or vapors may be present. <br /> Sparks and/or embers from power tools, burning cigarettes or pipes <br /> _c1" can Ignite fuels and their vapors. <br /> 1. Do not use electric power tools in areas where flammable vapors <br /> vb may be present. <br /> 2. Do not smoke in areas where flammable vapors may be present. <br /> To mount the piping sump sensor to vertical piping or conduit: <br /> 1. Attach a mounting strip to the top of the sensor using the 2 PlastiteTM screws pro- <br /> vided. <br /> 2. Wrap a second strip around the piping as shown in Figure 1 on page 8. <br /> 3. Using a 1/4-20 x 1/2-inch long screw and speed nut,attach the sensor mounting <br /> strip to the strip wrapped around the piping. <br /> 4. If necessary,carefully bend the mounting strip so that the sensor is in a true <br /> vertical position.Check the sensor to confirm that it is vertical and that it rests on <br /> the bottom of the sump. <br /> 5. Install the cord grip into the junction box. <br /> 6. Feed the sensor cable through the cord grip on the junction box. <br /> 7. Tighten the cord grip nut to ensure a water-tight seal at the cable entry. <br /> 9 <br />