Laserfiche WebLink
INVOICE #BG000486 TEST DATE: 02/11/99 <br /> UNDERGROUND TANK TESTERS <br /> PO BOX 3710 <br /> VISALIA, CA 93292 <br /> 209-747-5220 <br /> TANK STATUS EVALUATION REPORT <br /> ----------------------------- <br /> ***** CUSTOMER DATA ***** ***** SITE DATA ***** <br /> BANKS & CO JOE' S TRUCK STOP <br /> 2403 EAST BELMONT <br /> 15600 HARLAND RD. <br /> FRESNO, CA. LATHROP, CA. <br /> 93701 95332 <br /> CONTACT: MIKE CONTACT: BOB <br /> PHONE # : 485-3456 PHONE # : 982-0370 <br /> ***** COMMENT LINES ***** <br /> STEEL TANKS FIBERGLASS COATED DOUBLE WALL. <br /> CURRENT EPA STANDARDS DICTATE <br /> THAT FOR UNDERGROUND FUEL TANKS, THE MAXIMUM ALLOWABLE LEAK/GAIN RATE <br /> OVER THE PERIOD OF ONE HOUR IS . 05 GALLONS . <br /> TANK #1 : DIESEL FUEL 2 TYPE : STEEL RATE : . 003736 G. P .H. LOSS <br /> TANK IS TIGHT. <br /> TANK #2 : SUPER UNLEADED TYPE : STEEL RATE : . 021160 G.P.H. LOSS <br /> TANK IS TIGHT. <br /> TANK #3 : REG UNLEADED TYPE : STEEL RATE: . 001140 G.P.H. GAIN <br /> TANK IS TIGHT. <br /> TANK #4 : REG UNLEADED TYPE : STEEL RATE: . 020776 G.P.H. LOSS <br /> TANK IS TIGHT. <br /> F^'�j�y Ets �idl <br /> OPERATOR: SIGNATURE : v DATE . <br /> rt <br /> -------------------- - ------- 0 ��9� <br />