Laserfiche WebLink
PRECISION `� <br /> INDUSTRIES DIcEawJ <br /> O <br /> iUN , 1987 <br /> ENVIROM ENTAL HEALTH <br /> JUNE 2 , 1987 FERMI T/SERVICES <br /> INC. <br /> G E N E R A L SUN DIAMOND COMPANY <br /> ENGINEERING 1050 S . DIAMOND <br /> CONTRACTORS STOCKTON , CA 95205-7087 <br /> & S E R V I C E <br /> S T A T 1 0 N ATTENTION : RAY MARTINEZ <br /> MAINTENANCE <br /> LICENSE NO. 467293 LOCATION : SAME AS ABOVE <br /> RESULTS OF TANK TESTS PERFORMED MAY 28 , 1987 <br /> TANK #1 - 5 , 000 gallon unleaded fuel tank - <br /> Full system test indicated a volume change <br /> of - . 010 gallons per hour under test <br /> conditions . <br /> Full system test within state guidelines . <br /> TANK #2 - 125 gallon regular fuel tank - <br /> Full system test could not be completed <br /> due to a large loss of fluid during test <br /> period. <br /> Full system test failed state guidelines . <br /> RESULTS OF TANK TEST PERFORMED MAY 29 , 1987 <br /> TANK #3 - 500 gallon regular fuel tank - <br /> Full system test indicated a volume change <br /> of - . 023 gallons per hour under test <br /> conditions . <br /> Full system test within state guidelines . <br /> PRECISION INDUSTRIES , INC . <br /> WARREN DEE FOWLES <br /> FIELD SUPERINTENDENT <br /> WDF/psw <br /> 2191 NAVY DR.,STOCKTON,CALIFORNIA 95206 • 209/462-9911 - 800/332-5900 <br />