---------- <br /> NOTES: UST INSTALLATION bp <br /> _\ .......... <br /> SLOPE CONCRETE AWAY FROM ALL MANHOLES 1" RISE OVER 12" RUN. <br /> FIBER REINFORCEMENT TO BE USED, PREMIX UNIFORMLY THROUGHOUT <br /> CONCRETE, <br /> REINFORCING BARS TO BE NO LESS THAN 2" AND NO MORE THAN 4" FROM <br /> SURFACE, <br /> REINFORCE CONCRETE SLAB AROUND MANHOLE WITH (4) #4 REBAR 60" IN <br /> ------ LENGTH. PLACE REBAR 6" FROM SIDES OF BOX. <br /> _7N <br /> SINGLE 1" CONDUIT .TO EACH SUBMERSIBLE PUMP. PROVIDE SEAL.--OFF AT <br /> ------- <br /> y <br /> SUMP & BUILDING WIRING TROUGH. CONTAINS UNE VOLTAGE WIRING, ALL <br /> A 110N CAFjj <br /> 1 , oQ0 G �!AdTi <br /> <> <br /> 8" 3" 1 1 .-1 ROBROY PVC COATED CONDUIT <br /> CONDUIT PENETRATIONS MUST BE MADE WIT� <br /> Ju _D ----------- <br /> .......... ON LY, <br /> 1� ­­ - �__-___ 1-i...............------t___i. ­1--__, <br /> Ix -A uj -< 2 <br /> w 8" 8" <br /> =�V) e ANDARD MONITORING HOMERUN CONDUIT TO EACH TANK. <br /> B NE RESERVOIR 42" DIA. FILL SUMP - le 11 ONE 1" S1 <br /> ND INTERSTITIAL- TANK WEIGHT 1�oe <br /> 42 0R 48' DIA. FOR STANDARD MONITORING DEVICES, LOOP CONTAINMENT SL,,IMP <br /> TURBINE SUMP <br /> MONITOR 4,800 LBS DRY SENSORS, PLLD, VAC SENSORS & TANK GAUGE TO TANK INTERSTITIAL <br /> 4j (�j cp <br /> \ T (48" USED W/ 2 <6> SENSOR LOCATION AND HOMERUN T`0 BLDG. PROVIDE SEAT__-OFF"S IN <br /> 59950 LBS W/BRINE TURBINES) BUILDING & PRIOR TO LEAVING HAZARDOUS AREA. ROUTE' TO <br /> INTRINSICALLY SAFE TROUGH IN BUILDING. CONDUITS SHALL CONTAIN <br /> d <br /> E) FACE WIRING FOR SENSORS. ALL CONDUIT PENETRATIONS <br /> ARCO <br /> ------- ONLY LOW VOL <br /> MUST BE MADE WITH ROBROY PVC COATED CONDUIT ONLY. <br /> 0 <br /> 00 EP WEST 00Affr FCDJCYA U.0 <br /> \ �' - USE PEA GRAVEL, CONSISTING OF NATURALLY ROUNDED AGGREGATE, MIN <br /> 22" DIA, & MAX OF IN SIZE, FREE OF CLAY, SLAG, CINDERS, OR DEBRIS, ALL <br /> 104 ANCHOR S TRAP <br /> LOCATION (TYP.) <br /> MANWAY <br /> TANK LIFTING LUGS SUBSTITUTES MUST BE APPROVED BY MANUFACTURER'S & OWNER'S FIELD <br /> \ --(Typ.) <br /> REPRESENTATIVE, <br /> 0 NOT USED. <br /> \ r"'' ��> <br /> NOT USED. <br /> -HE FOOTPRINT OF THE TANKS. REQUIRED TO PROVIDE FOR PROPER <br /> ----------- L TANK PAD MINIMUM 2'--0" OFF OUTSIDE WALLS OF TANKS, AND MUST 0 <br /> ------ COVER 1 0 <br /> _j <br /> TANK HOLD DOWN, AND TO PRE-VENT ACCIDENTAL DRILLING INTO TANK. <br /> co <br /> 11 CUT CORNER WHERE MEETING ASPHALT PAVING ONLY. SQUARE CORNERS <br /> ----------------------------- ------------ .......... <br /> WHERE MEETING CONCRETE, <br /> 16­1/2"� ------- E N <br /> 11 1/8" 10001--_---------------------01 REFER TO SITE SPECIFIC PLANS FOR ACTUAL PIPE RUNS & NUMBER OF <br /> > PRODUCT LINES (1 OR 2 PER UST SUMP), <br /> (Typ') 18215 72ND AVENUE SOUTH <br /> 'TURBINE AND FILL SIDE SUMP CONFIGURATION SHOWN IS TYPICAL, FOR KENT, WA 98032 <br /> SPECIFIC DESIGN CRITERIA AF THESE SUMPS SEE ACCOMPANYING TANK (425)251.--6222 <br /> 3'--3 7/8" 84-3" 7 --4 1/4" 8'_3°F 3'--3 7/8" INSTALLATION SITE PLAN & SUMP DETAIL. DRAWINGS NOTED ABOVE, (425)251-8782 FAX <br /> ---------- ----------------- <br /> _1�--------------- --- -------_-- <br /> 30'-6" <> TANK ANCHORING OPTIONAL, CONSULT LOCAL, REGULATION; VERIFY WITH UAL ENGINEERING, LAND PLANNING, <br /> ............... ------ ------------------------------------ ----------------- OWNER'S REPRESENTATIVE, SURMING, ENVIRONMENTAL SERVICES <br /> OVERFLOW PROTECTION: UST OVERFLOW COMPLIANCE IS ACHIEVED BY USE OF <br /> _.,<�>OPTIONAL MANUFACTURER SUPPLIED OVERFLOW PREVENTION DROP TUBE FLAPPER VALVE SET AT 95% AND IS IN NO" DATE REVSION DESCRIP'OON <br /> 12"x12"x16' DEADMAN ACCORDANCE WITH FEDERAL AND STATE GUIDELINES FOR UST OVERFILL 02/25/16 PLAN REWW MWDn <br /> UNDERG""ROUND TANK PLAN VIEW (TYP. OF 4) REQUIREMENTS, <br /> AE 10/4/16 AGENMVOWNER REVS <br /> SCALE: 1/2" l '-.0" AN OVERFILL Al.-ARM AND ACKNOWLEDGE SWITCH TIED INTO THE VEEDER ROOT Z, <br /> "\ 10/27/16 AGENC`( REVS <br /> AUTOMATIC 'TANK GAUGE SYSTEM, THE MONITORING SYSTEM PROVIDES AN ------------- <br /> D E F AUDIBLE AND VISUAL ALARM WHEN THE TANK(S) ARE FILLED TO THE 90% <br /> FOR OPW FILLS -w - <br /> 3714 J W .3.14 1 FOR SINGLE IST & SINGLE UST A-L <br /> ._(M._5� ----------------------------------------------- <br /> _3 <br /> (2012 CONFIGURATION) X INDICATES ITEMS FOUND ON MATERIALS LIST SHEETS M,5.3,01 & M,5,3,02 <br /> 0� <br /> D E IF <br /> FOR FRANKLIN FUELII <br /> SYSTEMS FILLS Z.1 M.5...17 M,5,117 ------- ...... ­­_A-L-11-1-1 <br /> NOTE: �2 <br /> CHOSE APPLICABLE DRAWINGS <br /> 3 --\, FOR CONFIGURATION, A-p <br /> ------------------------------------------------ <br /> AND STONE PER G 4 3 4 (TYP.) __0 Ag <br /> PROJECT SPECIFICATIONS 345 <br /> 10 11 (TYP.) 7" CONCRETE SLAB AT <br /> <� 10, 1 _i� <br /> <1> (1-yp,) 87.6 LB/CF <br /> (T),p ------------- SEAU <br /> .......... <br /> (2) <br /> 15' DIA, <br /> SUMPS <br /> .............. <br /> 3" PEA GRAVEL MIN, TO CHRIS M. TE�A,�ql""",,, <br /> Y <br /> PREVENT LOAD -TRANSFER <br /> 1 COND° LOOP TO SUMP - ... \" -\\r -<D24' Mk cuq15 <br /> J-BOX TO TOP OF TANK COVER <br /> 'FAN K <br /> 4" FRP RISER TO 47, < -7 0 DEPTH jj <br /> GRADE ------6" WIDE DETECTABLE L�kRGROUND R >_ I/ 1 4 <br /> MARKING TAPE BURIED 6"­12" fy- 8,0' DIA, .............. ........ (4 p <br /> -.-.) 4,800 LBS _�1,0' GRAVEL < <br /> DUAL FLOAT HYDROSTATICBELOW FINISHED GRADE: EMPIRE COLUMN c I v <br /> n m <br /> ---------- MAGNA TEC #31---143 <br /> MONITORING SENS( IF 5 ()F' C <br /> 6 <br /> op <br /> (> HOME RUN TO 1341" FRP BONDED 1,0' x 1°0' X 32V <br /> 6 <br /> BL ___�124)ENTRY FITTING DEADMAN <br /> J ------ <br /> HYDROSTATIC (Typ�) <br /> 7­ <br /> RESERVOIR <br /> 1 o'_0 12" <br /> SLOPE SIDES OF TANK HOLE OR <br /> -IONS <br /> USE SHORING FOR ALL TANK BUOYANCY CALCLJI.-AJ <br /> EXCAVATIONS IN ACCORDANCE' WITH <br /> CALCULATION BASED ON SUBMERGED WEIGHT OF MATERIALS: <br /> OSHA 1926 SUBPART P, OSHA 1" FRP BONDED(DS4. <br /> r <br /> STANDARD S - EXCAVATIONS; FINAL_ ENTRY FITTING TANK WITH SPHERICAL ENDS, 8.0' O.A. DIA, (8' NOMINAL.) <br /> TANK DIAMETER 8'­0" <br /> RULE OCTOBER 1, 1989 ---------- ......... ANCHOR STRAP TANK LENGTH: 30' 1 <br /> F <br /> j <br /> -<4>LOCATION (TYP.) TRY 32'--0" DEADMAN, EACH SIDE, 12" WIDE X 12" HIGH <br /> q EXT�ACI`OR FI­IN DEVELOPMENT INFORMAnON: <br /> EMPTY TANK UPLIFT' 10,000 GAL <br /> 'VE T�64 <br /> 6 F F11 L PROT <br /> X <br /> DR F' TU AT 7.48 GAL./CF <br /> ARCO Nfl <br /> BACKFILL, LTH 1,337 CU FT <br /> X/, <br /> X <br /> X <br /> 37 CU FT' X 62A <br /> PEAGRAVEL E. TANK! -yp,) <br /> 0�\ ".�% -0 ;,L)7. (1 6 <br /> /�X/ Al LESS ( F 83,429 LBS (DISP(ACED WATER) 3000 am/pm <br /> MAN UFACTU RER 2 <br /> 1 \611^5j\>- <br /> 4'V 00 TANK SUMP UPLIFT (2) X 3,14 <br /> SPECIFICATI)NS (TYP X 1.7 5' X 4' 7 6,9 C U FF <br /> FUEL CANOPY <br /> 12 24"x fll GA) STEEL w/ 6 MPD's <br /> 00 <br /> ST ;KER LAT _ER) <br /> \, \ FEEL STRI(ER PLAFEB 76,9 CF X 62.4 L.BS/CU FT 4,799 LBS (DISPLACED WAI <br /> TANK 1.EVEL GALIGE vv <br /> 12"x 1 2"x 11 A (S TYF,� <br /> -TYR UND_R ALL 01`11�.NINGS 1 W/�� <br /> 04 <br /> ENING S W/ <br /> c <br /> TAN 2" FLOAT KIT. OVERFILL� <br /> MA'NW,' �ON Fl.-�ER��LASS i MANWAYS:ON FIBERGLASS TOTAL TANK UPLIFT 83,429 LBS + 4,799 LBS 88- 228 LBS <br /> \\\! \ 05 ALARM AT 90% CAPAC0 <br /> Y TANK M NF SITE ADDRESS� <br /> TANK <br /> HQL2 <br /> _QQW_N_&_AjS,QLAI-01 <br /> (BY TANK' MA IF�) <br /> \X X/ 15 g, <br /> (DTANK SLAB: .58' X 1 OV X 345 200,1 CU FT E90ALON AVENUE <br /> 0 X/ <br /> 2001 CU FT X 87.6 LBS CU FT 1�7 <br /> 5 LHSFKV-WAY 120 <br /> \ \ °," ° \ 'SCALORCA <br /> Z ...... F <br /> -- ----- ------- X� m C2) CUBED BACKFILL ABOVE TANK: <br /> xK <br /> 4' X 8.0' X 305 976 CU FT - 76.9 CU FT 99,1 CF <br /> \�x <br /> QCURVED BACKFILL ABOVE TANK: <br /> 4- <br /> .................... 8991 CU FTX 57.6 LBS/ CU Fl 1,.Z8d tr <br /> > FACILITY # TBD <br /> 2 DESIGNED BY. ALUANCE Z&DM, <br /> 3 '14 X 4.0' X 305 1,532�3 CU FT <br /> x <br /> V-0" MIN, PEA GRAVEL 7 <br /> IT <br /> DiECKED ft, BP REPM: <br /> ov <br /> TRAPPER SCREEN <br /> 8V x 8,0, X '305 1,952 CU FT <br /> atm <br /> "> INSTALLED OVER <br /> -__-------------------- ------......... <br /> TANK SHALL BE SET' DEAD LEVEL x <br /> COMPACTED SOIL <br /> 'U FT 4193 C U FT <br /> ------ 1,952 CU FT - 1,532,3 C <br /> I 209�9 CU FT DRAWN BY, AUJANM PM: <br /> �X/,\0Xx 2 <br /> _F L <br /> 209.9 CU FT X 57,6 LBS/ CU F ?,090 LBS I&RSION: PROJECT NO- <br /> V-12 0 <br /> _7\ <br /> NATIVE VIRGIN SOIL <br /> GRAVEL. COLUMN ABOVE DEADMEN: <br /> \1 /x <br /> 17,223 <br /> END OF 'TANK 1,0' X 12.0' X 32,0' X 2 = 768�O CU FF <br /> 0 <br /> 2' MIN. TANK SIZE VARIES WITH MANUFACTURER AND MODEL NUMBER 2' MIN. 76&0 CU FT X 57,6 LBS/ CU FF �44 ?,37 <br /> ------------------------------------------------------------------------ ------- -------------------------------__ ...........................................- - ------------------- --------------------------------- - - ---------------------------------------------------------------------------------------------------------------------------------- --------------------- -—------------___-__-__ -------_-----_----__--_ <br /> .............. IK � <br /> CONCRETE DEADMEN: 'TYPICAL 10,000 GALLON <br /> 10 00 1 V X 1,0' X 32V = 32.0 CU FT DOUBLE WALL FIBERGLASS TANK <br /> 32.0 CU FTX 87"6 L.BS/ CU FT X (2) = 5,6k LBS AILS <br /> INSTALLATION DET <br /> DRY WEIGHT OF TANK: <br /> ------- SHEET �707_ <br /> .......... TOTAL HOLD DOWN: 1 05 1,13- <br /> TOTAL HOLD DOWN: 13.(�L05-0_IB i 1,54 SAFETY FACTOR <br /> TOTAL TANK UPLIFT: 88,228 LBS <br /> 4 <br /> BUOYANCY CALC, 10,000 GAL.. TANK <br /> Aw <br /> wUNDERGROUND TANK SECTION DETAIL <br /> Mm5m3mO5 <br /> SCALE: 1/2" = 1 0" SCALE: NTS <br />