Laserfiche WebLink
Hazardous Waste Tank Syst..., <br />Written Assessment per CCR Title 22 <br />Chase Chrysler Jeep, Stockton, CA <br />Seismic/Anchoring findings: The tank as desig <br />containment area in which it is located are adequE <br />seismically sound. Initials: <br />Leak Test: <br />March 9, 2011 <br />and operated, and the <br />anchored and are <br />The tank has been in service for 17 years and shows no evidence of <br />leakage. The tank is a UL Listed Tank. UTG measurements show the <br />tank wall thickness is greater than the UL Standard minimum thickness <br />requirements of 0.093". <br />UTG Thickness readings: <br />UTG Measurements <br />Waste Antifreeze mm <br />in <br />Point ID Thickness <br />1 2.76 <br />2 3.22 <br />3 3.52 <br />4 2.78 <br />5 2.78 <br />6 2.77 <br />7 2.71 <br />8 3.32 <br />9 2.82 <br />10 2.86 <br />11 2.71 <br />12 3.3 <br />13 2.83 <br />14 3.33 <br />15 2.78 <br />16 3.39 <br />17 3.41 <br />18 3.41 <br />19 3.98 <br />20 3.7 <br />21 3.74 <br />22 3.46 <br />23 2.9 <br />24 2.87 <br />25 2.84 <br />26 2.76 <br />27 3.08 <br />28 3.58 <br />29 3.76 <br />30 <br />aeg 3.15068966 0.124043 <br />std dev 0.387057871 0.015238 <br />Strandberg Associates 1(866) 388-0404 (650) 329-8918 rwaterguy(a),rwaterguy.com 26 <br />