Laserfiche WebLink
E <br />N <br />R <br />E <br />N <br />Ci <br />G <br />I <br />N <br />C <br />2 <br />L <br />5 September 2, 1986 <br />P City of Lodi <br />A 221 West Pine Street <br />C <br />I Call Box 3006 <br />F Lodi, California 95241-1910 <br />1 <br />C Attn: Dick Wiech <br />V Re: Petro -Tito Tank Test 3 <br />E <br />Dear Dick: <br />`l On September 2, 1986, we performed a Petro-Tite Tank Test <br />at 1331 _So_. Ham Lane, Lodi, California. The test was per - <br />S formed by Robin Olson, E.P.E. Technician. The NFPA code <br />329.02 criteria for a tight tank system is a tolerance of <br />X +-.050 gallons per hour. Because of the almost infinite var- <br />iables involved, this is not intended to be a mathematical <br />tolerance and is not the permission of actual leakage. <br />7 <br />6 PRECISION TEST <br />S Tank l - East <br />T Size - 10,000 gallon tank <br />O Product - Regular <br />C The test showed a positive .015 gallons per <br />K hour. Based on the above criteria, we find <br />T the tank system tested mathematically tight. <br />O <br />N <br />This concludes our test and findings on September 2, 1986. <br />C If you have any questions regarding the results, please con- <br />A tact me. An extra copy has been included for you to notify <br />9 your local County Health Department, Environmental Health. If <br />5 you have any questions on what your next step should be, please <br />2 contact your local Health Department immediately. <br />0 <br />j Sincerely, <br />2 <br />2 / �� f � <br />9 Robin Olson <br />9 Certified Tank Testing Technician <br />4 <br />3 <br />1 RO/bm <br />0 <br />2 Encl. <br />2 <br />