Laserfiche WebLink
City of Lodi <br /> UST CATHODIC PROTECTION SURVEY DATA <br /> Tested by: Ron Bianchetti, P.E. CP SPECIALIST#8429 <br /> Date: 3/4/2005 <br /> CATHODIC PROTECTION SYSTEM <br /> PERFORMANCE DATA SHEET <br /> TEST WIRE Potential Current VENT Comments <br /> #/Color (Volts) (mA) <br /> STRUCTURE <br /> Location: <br /> Municipal Service Center <br /> Waste Oil Tank S/E of Service Bas Black -1.292 0.5100 Fiberglass Repairs implemented cathodic protection system is <br /> Black -1.287 05660 now functioning properly <br /> White(Test) -0.972 <br /> Fill Tube -0.972 <br /> Supplemental Current Requirement Testing <br /> As-found W/Current Applied <br /> Unleaded Tank East Fill Tube -0.265 -0.321 Fiberglass Cathodic Protection System is not functioning ro erl . <br /> Temporary Current Testing with current of Test -0.261 -0 321 Low potentials due to interconnection to electrical ground <br /> 0.53 amperes applied through metallic conduit. Locate short and isolate. <br /> Current again confirm that a short exists to through the ground I <br /> TABLE 2 <br />