J <br /> March 25, 2005 <br /> City of Lodi <br /> 221 West Pine Street <br /> Lodi, CA 95241-1910 <br /> Attention: Mr. Mark Zollo <br /> Reference: Cathodic Protection System Inspection <br /> Municipal Service Center Underground Storage Tanks (UST) <br /> 1331 S. Ham Lane <br /> Lodi, California <br /> Dear Mr. Zollo: <br /> On February 18, 2005, Blackstone Group, Ltd. (BGL) conducted an initial evaluation of <br /> the cathodic protection systems on the referenced UST. Due to some necessary repairs <br /> additional testing and evaluations were performed on March 4 and March 25, 2005. <br /> BACKGROUND: <br /> The Underground Storage Tanks were tested to evaluate the effectiveness of the cathodic <br /> protection systems and are as follows: <br /> • Municipal Service Center. Four Tanks (Figure 1) <br /> • 2- Unleaded Tanks <br /> • 1- Diesel Tank <br /> • 1- Waste Oil Tank <br /> Each location was initially designed with a sacrificial type cathodic protection system. <br /> The tank manufacture supplied the tanks with STI-P3 installed zinc anodes and contractor <br /> installed supplemental magnesium type anodes. Each of the zinc anodes are attached <br /> directly to the tank and the remaining magnesium anodes installed around the perimeter <br /> of the tanks. The magnesium anode wires are routed into the fuel tank pit and terminated <br /> on a test board (Figure 2) <br />