TEST RESULTS <br /> Data for our testing are tabulated on the attached sheet. Test wire voltages with less than <br /> —1.0 volts are not functioning. The data in the "Tank ON" column indicates the levels of <br /> CP for each tank with the system connected. The data in the "I" column indicates the total <br /> current presently being supplied by the anodes. <br /> CONCLUSIONS <br /> Analysis of this data indicates that all tanks at the Public Safety Building and Municipal <br /> Service Center are more negative than —0.850 volts and meet or exceed the <br /> aforementioned criteria. This indicates that the tanks are receiving proper levels of CP at <br /> this time. <br /> RECOMMENDATIONS <br /> While the Environmental Protection Agency (EPA) regulations mandate testing <br /> conducted on three-year intervals to determine the effectiveness of the installed systems, <br /> experience and good engineering practice dictate that an assessment be made on an <br /> annual basis. This interval will also monitor the life expectancy of these magnesium <br /> anodes recently connected. We would recommend an annual assessment for the next one <br /> to two years to trend the performance of the system. Estimated costs to test the systems <br /> and provide a report is $600.00. <br /> The annual inspection of the cathodic protection systems should consist of structure-to <br /> soil potential measurements, current output of the anode beds, and a summary report to <br /> include field data and recommendations as required. <br /> We appreciate this opportunity to be of service to you on this project and look forward to <br /> working with City of Lodi on future projects. If you have further questions or desire <br /> additional information please contact us at (925) 736-0783. <br /> Sincerely, <br /> Blackstone Group Ltd. <br /> v' <br /> onald L. Bianchetti, P.E. <br /> President <br /> 2 <br />