SWRCB, January 2002 <br />7. UNDER -DISPENSER CONTAINMENT (UDC TESTING <br />Page of <br />Test Method Developed By: UDC Manufacturer Industry Standard X Professional Engineer <br />L Other (Spec) <br />Test Method Used: ❑ Pressure 0 Vacuum X Hydrostatic <br />0 Other (Specify) <br />Test Equipment Used: Caldwell Level Change Indicator Equipment Resolution: .002 <br />UDC # 4&5 <br />UDC # <br />UDC # <br />UDC # <br />UDC Manufacturer: <br />Western Fiber lass <br />DC Material: <br />Fiber lass <br />DC De the <br />28" <br />ight from UDC Bottom to Top <br />Hi hest Pi in Penetration: <br />r <br />10" <br />ight from UDC Bottom towest Electrical Penetration: <br />Condition of UDC prior to <br />testing: <br />Dry <br />Portion of UDC Tested' <br />Water Level 14" <br />Does turbine shut down when <br />UDC sensor detects liquid (both <br />pro and water)?* <br />Yes <br />Turbine shutdown response time <br />Not Alarmed <br />Is system programmed for fail- <br />safe shutdown?* <br />Yes <br />Was fail-safe verified to be <br />operational?* <br />No <br />Wait time between applying <br />water and starting test <br />5 Minutes <br />Test Start Time: <br />3:27 <br />Initial Reading Ri): <br />.001 <br />Test End Time: <br />3:57 <br />Final Reading (RF): <br />.001 <br />Test Duration: <br />30 Minutes <br />Change in Reading RF-Ri : <br />0 <br />Pass/Fail Threshold or Criteria: <br />.005/30 Minutes <br />Test Result: <br />Pass <br />Was sensor removed for testin ?Yes <br />Was sensor properly replaced and <br />verified functional after testing? <br />Yes <br />Comments — (include information on repairs made prior to testing and recommended follow-up forfailed tests) <br />Initial loss due to Seam on Test Boot on Regular 87 Secondary Pipe. <br />Removed Test Boot in UDC. Secured Test Boot on Secondary Pipe in STP Piping Sump, and filled UDC to test level. <br />This method allows Test Fluid to fill UDC and Secondary Pipe simultaneously. <br />Secondary Pipe Test Boot at STP Piping Sump opened at end of testing to allow all Test Fluid to drain. <br />' If the entire depth of the UDC is not tested, specify how much was tested. If the answer to any of the questions indicated with an <br />asterisk (*) is "NO" or "NA", the entire UDC must be tested. (See SWRCB LG -160) <br />