SANJ O 1` Q U I `IA,II, Environmental Health Department <br /> COUNTY <br /> Aboveground Petroleum Storage Act Inspection Report <br /> Facility Name: Facility Address: Date: <br /> AMERON INTERNATIONAL 10100 W LINNE RD,TRACY January 08, 2019 <br /> Other Violations <br /> 4030 See below Unlisted Operations/Maintenance violation ❑V ❑R ❑COS <br /> 4040 See below Unlisted Release/Leaks/Spills violation ❑V ❑R ❑COS <br /> 4050 See below Unlisted Abandonment/Illegal Disposal/Unauthorized Treatment violation ❑V ❑R ❑COS <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 301 CFR 112.5(a) Failed to amend Plan as necessary. <br /> The SPCC plan does not address all APSA qualified tanks. The SPCC plan failed to address an emergency <br /> generator with a belly tank containing diesel and capacity which appears to be over 55 gallons. Operational <br /> equipment in the Bell Expander and Hydrotest areas were not addressed in the SPCC plan. The operational <br /> equipment consists of two hydraulic fluid reservoirs of 300 gallons and another that may be between 400 and 500 <br /> gallons. The area referred to as the Hazardous Waste consolidation area was observed with several 55 gallon <br /> drums, some of which were described as containing oily water and is not addressed in the plan.The Spill <br /> Prevention, Control, and Countermeasure(SPCC) Plan must be amended when there is a change in the facility <br /> design, construction, operation,or maintenance that materially affects its potential for a discharge,within 6 months <br /> of the change, and implemented as soon as possible, not later than 6 months following preparation of the <br /> amendment. Immediately make all necessary amendments to the SPCC Plan to accurately represent the <br /> procedures and policies currently in place at the facility. Include all aboveground petroleum storage tanks with a <br /> capacity of 55 gallons or more. <br /> This is a minor violation. <br /> 602 CFR 112.7(a)(2)Plan failed to discuss equivalent environmental protection, if applicable. <br /> The Spill Prevention, Control, and Countermeasure(SPCC)failed to discuss alternative environmental protection <br /> requirements. The SPCC plan states that the 300 and 500 gallon tanks along with some 55 gallon drums do not <br /> have overfill protection as required by CFR 112.8(c)(8). The SPCC plan does not give the reasons for <br /> nonconformance and a detailed description of the alternate method is not discussed. Table 6 of the SPCC plan <br /> states that the 300 and 500 gallon tanks do not require inspections, given the use of environmental equivalent <br /> measures described in section 5.4 of the SPCC plan. Section 5.4 of the SPCC plan does not discuss the reasons <br /> for nonconfomance and fails to describe a detailed alternative method. If the SPCC Plan does not conform to the <br /> applicable requirements,the reasons for nonconformance must stated and the alternate methods to achieve <br /> equivalent environmental protection must be described in detail in the Plan. Immediately amend the SPCC Plan to <br /> include a discussion of equivalent environmental protection. <br /> Note: <br /> Requirements for overfill prevention per CFR 112.8(c)(8). <br /> (i) High liquid level alarms with an audible or visual signal at a constantly attended operation or surveillance station. <br /> In smaller facilities an audible air vent may suffice. <br /> (ii)High liquid level pump cutoff devices set to stop flow at a predetermined container content level. <br /> (iii)Direct audible or code signal communication between the container gauger and the pumping station. <br /> (iv)A fast response system for determining the liquid level of each bulk storage container such as digital computers, <br /> telepulse, or direct vision gauges. If you use this alternative, a person must be present to monitor gauges and the <br /> overall filling of bulk storage containers. <br /> This is a Class II violation. <br /> FA0004382 PR0515795 SCO01 01/08/2019 <br /> EHD 28-01 Rev.09/27/2018 Page 4 of 6 Aboveground Petroleum Storage Act OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjcehd.com <br />