CLASS II VIOLATION #706 <br /> CFR 112.8(c)(2) Failed to provide and maintain adequate <br /> secondary containment. The emergency generator was observed <br /> with insufficient secondary containment. There was no evident <br /> secondary containment for the belly tank of the generator. All bulk <br /> storage tanks must be provided with a secondary means of <br /> containment for the entire capacity of the tank and sufficient freeboard <br /> to contain precipitation. <br /> Corrective Action <br /> Northwest Pipe Company hereby commits to custom fabricate <br /> containment with a capacity of —100 gallons, enough to contain the <br /> entire capacity of the 80 gallon belly tank plus sufficient freeboard to <br /> contain precipitation. <br /> ................................................................................................................................................... <br /> Northwest Pipe Company <br />