OPEN CLASS II VIOLATION #602 <br /> CFR 112.7(a)(2) Plan failed to discuss equivalent <br /> environmental protection, if applicable. <br /> The SPCC plan failed to discuss alternative environmental protection <br /> requirements. The SPCC Plan states that the 300 and 500 gallon <br /> tanks along with some 55 gallon drums do not have overfill <br /> protection as required by CFR 112.8(c)(8). If the SPCC Plan does not <br /> conform to the applicable requirements, the reasons for <br /> nonconformance must [be] stated and the alternate methods to <br /> achieve equivalent environmental protection must be described in <br /> detail in the Plan <br /> . ................................................................................................................................................ <br /> ® Northwest PipeCompaay <br />