Laserfiche WebLink
American Biodiesel lmpi Silo S-1 <br /> Stockton,CA g ^?= Out of Service Inspection <br /> 8.1 Silo UT Survey continued <br /> UT Readings <br /> Location# (in.) <br /> 40 0.233 <br /> 41 0.245 <br /> 42 0.240 <br /> 43 0.237 <br /> 44 0.240 <br /> 45 0.245 <br /> 46 0.228 <br /> 47 0.248 <br /> 48 0.243 <br /> 49 0.245 <br /> 50 0.243 <br /> UT Summary <br /> Minimum 0.219 <br /> Maximum 0.252 <br /> Average 0.237 <br /> 8.2 Silo Nozzle UT <br /> Pipe <br /> Size Top Right Bottom Left Comments <br /> Item Description in in in in in <br /> A Manway 20 0.198 0.207 0.188 0.206 - <br /> B Nozzle 4 0.194 0.192 0.190 0.180 Temperature transmitter <br /> C Nozzle 3 0.155 0.177 0.186 0.152 - <br /> D Nozzle 3 0.179 0.190 0.179 0.193 - <br /> E Nipple 3 0.114 0.148 0.115 0.125 Free vent <br /> This is a welded flange to <br /> F Nozzle 4 N/A N/A N/A N/A bottom of cone- UT readings <br /> not obtainable <br /> 8.3 Shell Plate UT <br /> The following table details the lowest single point UT readings obtained from the silo UT survey. The included <br /> silo layout drawing details the location of each UT reading. <br /> Course <br /> No. Scan 1 Scan 2 Scan 3 <br /> 3 0.229 0.231 0.219 <br /> 2 0.227 0.234 0.246 <br /> Cone 0.227 0.240 0.242 <br /> Report Date Petroleum&Refractory, Inc. Page 12 of 21 <br /> March 6,2007 TankReporter 13.91 <br />