Laserfiche WebLink
SANJ O 1` Q U I `IA,II, Environmental Health Department <br /> COUNTY <br /> Aboveground Petroleum Storage Act Inspection Report <br /> Facility Name: Facility Address: Date: <br /> Ramos Oil Co- 1505 Navy Drive 1 1505 Navy Dr, Stockton January 14, 2019 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 604 CFR 112.7(a)(3)(i)Plan failed to include oil type and storage capacity for each container. <br /> The type of oil and storage capacity for each container or provide an estimate of the potential number of mobile or <br /> portable containers,the types of oil, and anticipated storage capacities was not provided for 55 gallon drums <br /> mentioned in the SPCC plan. The type of oil in each fixed container and its storage capacity. For mobile or portable <br /> containers, either provide the type of oil and storage capacity for each container or provide an estimate of the <br /> potential number of mobile or portable containers,the types of oil, and anticipated storage capacities; <br /> This is a minor violation. <br /> 607 CFR 112.7(a)(3)(iv) Plan failed to include countermeasures for discharge discovery, response and cleanup. <br /> Countermeasures for discharge discovery, reposnse and cleanup up was not addressed for the pipe trench in <br /> between the despensers.Address in the SPCC plan, countermeasures for discharge discovery, response, and <br /> cleanup(both the facility's capability and those that might be required of a contractor).Amend the SPCC Plan to <br /> include discussion of all applicable regulations. <br /> This is a minor violation. <br /> 706 CFR 112.8(c)(2)Failed to provide and maintain adequate secondary containment. <br /> Appendix D of the plan, "SPCC Contingency List"describes the secondary containment wall for the two 10,000 <br /> gallon diesel tanks as not being sufficient and the wall needed to be raised by approximately 5 inches. The two <br /> 10,000 gallon tanks appeared to be permanently manifolded. All bulk storage tanks must be provided with a <br /> secondary means of containment for the entire capacity of the tank and sufficient freeboard to contain precipitation. <br /> Immediately provide sufficient secondary containment for this and all other tanks at this facility. <br /> Note: Permanently manifolded tanks are tanks that are designed, installed,or operated in such a manner that the <br /> multiple containers function as a single storage unit(67 FR 47122, July 17, 2002).Accordingly,the total capacity of <br /> manifolded containers is the design capacity standard for the sized secondary containment provisions(plus <br /> freeboard in certain cases). <br /> This is a repeat violation, Class ll. <br /> 710 CFR 112.8(c)(6)Plan failed to adequately discuss procedures to test or inspect each container for integrity. <br /> The SPCC plan references STI SP-001 industry standard for testing and inspections. The qualifications of <br /> personnel performing tests and inspections,frequency and type of testing and inspections taking into account <br /> container size, configuration, and design are not determined in accordance with industry standards.The <br /> qualifications of personnel performing tests and inspections,frequency and type of testing and inspections that take <br /> into account container size, configuration, and design shall be determined in accordance with industry standards. <br /> Examples of these integrity tests include, but are not limited to:visual inspection, hydrostatic testing, radiographic <br /> testing, ultrasonic testing, acoustic emissions testing, or other systems of non-destructive testing. Comparison <br /> records and other records of inspections and tests must be maintained on site. Immediately amend the SPCC plan <br /> to include discussion to meet the requirements of this section and conduct the necessary testing, if needed. If <br /> testing is conducted, submit a copy of the test results to the EHD, or provide equivalence as allowed by CFR <br /> 112.7(a)(2). <br /> This is a repeat violation, Class Il. <br /> FA0020706 PR0536585 SCO03 01/14/2019 <br /> EHD 28-01 Rev.09/27/2018 Page 5 of 7 Aboveground Petroleum Storage Act OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjcehd.com <br />