Laserfiche WebLink
Test Protocol (cont.) <br /> 9. Inspection of the primary steel :ank - <br /> "i. At this point the inspector should locate and note the leak detection port. <br /> ii. The integrity of the inner steel primary tank is accomplished by checking for fluid between the steel tank and the <br /> HDPE liner.See below. <br /> Cross Section of ConVaolt <br /> All <br /> Interstice(between <br /> Primary and Secandary) <br /> Case:Reel wrik is uncompromised <br /> Result Fuel remains safely stored Intank <br /> The inspectorshould obtoin o clean woodorioUtic inspection(non-pointed)rod ofsufficient length to reach the full depth <br /> of the innersteel tank.With the inspection port cap opened,insert the rod to the bottom of the tube. <br /> iii. Withdraw the inspection rod and visually examine it. <br /> a. If the rod Is dry and there is no liquid present then the primary steel tank is not leaking and the ConVault <br /> Is suitable for continued use. <br /> Seenexrpage ifthe rod is wet. <br />