JAN 2 3 2019 <br /> Item #304 — The dispenser #3/4 208 sensor failed to activate an audible and visual <br /> alarm when tested to ensure continuous monitoring of the tank system. <br /> On 01/29/2018, BP testing and maintenance vendor, Gettler-Ryan, Inc., replaced the <br /> sensor which subsequently passed the retest. This item was corrected onsite. A copy of <br /> the UST Monitoring System Certification report is enclosed herein for your records. <br /> Item #313— Seepage was observed on the diesel pipe in the dispenser#4, indicating a <br /> leak in the primary piping. <br /> On 02/06/2018, BP testing and maintenance vendor, Gettler-Ryan, Inc., arrived onsite to <br /> investigate the issue but needed to return to the site to make the necessary repairs. On <br /> 02/08/2018, Gettler-Ryan, Inc., returned to the site, cleaned the diesel shear valve, <br /> union, and piping, but ultimately found no leaks. The technician is stating it is possible <br /> when the filters were changed, diesel may have spilled onto the union and shear valve. <br /> A copy of the work orders are enclosed herein for your review and records. <br /> Item #316 — Water was found in various sumps and UDC. Liquids were observed in <br /> various sumps and UDCs. <br /> On 02/06/2018, BP testing and maintenance vendor, Gettler-Ryan, Inc., arrived onsite to <br /> check all sumps and UDCs for liquids but needed to return to the site to make the <br /> necessary repairs due to sump depth. On 02/08/2018, Gettler-Ryan, Inc., returned to <br /> the site, cleaned all liquids using rags, and placed the used rags in the site's hazardous <br /> waste drum. The technician is stating the liquids were not fuel but appeared to be brine <br /> solution. A copy of the work orders are enclosed herein for your review and records. <br /> It is our policy to operate in full compliance with all laws and regulations at our retail facilities. <br /> However, when we fall short of perfection, we endeavor to immediately address deficiencies, <br /> issues of concern, and/or agency requests regarding our retail facilities. With the submittal of <br /> this letter, it is our understanding that the item(s) of alleged non-compliance have been <br /> resolved and no further corrective action is required. Furthermore, we understand that there is <br /> no fine or penalty associated with this violation. If this is not correct, please contact me as soon <br /> as possible. If you have any questions or require additional information, please contact me at <br /> 415-902-5089 or Daryl.Lee@bp.com. <br /> BP Products North America Inc. reserves all of its rights and defenses associated with this <br /> matter. <br /> Regards, <br /> Daryl Lee <br /> Retail Compliance Coordinator <br /> Enclosures <br />