Laserfiche WebLink
SAID JOAQIJIN Environmental Health Department <br /> ---C C)u N I -2 -1 <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> ARCO 06080 85 E LOUISE AVE, LATHROP January 22, 2019 <br /> Item# Remarks <br /> 113 CCR 2638(c), 2638(d) Failure to submit"Monitoring System Certification Form" within 30 days of completion of the <br /> test. <br /> Annual monitoring system certification, leak detector testing, and spill container testing was performed on January <br /> 29, 2018 and a test report was submitted on March 2, 2018, more than 30 days of the test. A copy of the test report <br /> must be submitted within 30 days of the tests. Take all necessary precautions to ensure testing and submittal of <br /> test reports are performed in a timely manner. <br /> This is a Class II violation. <br /> 121 CCR 2712(f) Failed to submit a written response within 30 days of receiving an inspection report. <br /> An inspection was last done on January 29, 2018 and an inspection report was issued identifying information to be <br /> submitted to bring this site into compliance. During the January 29, 2018 inspection, water was found in the diesel, <br /> 87, and 91 submersible turbine pump (STP) sumps, 87 and diesel fill sumps, vent box sump, and under dispenser <br /> containment (UDC) sump in dispenser#3/4. The received return to compliance documentation did not adequately <br /> address this violation. This information was required to be submitted by March 1, 2018. The adequate return to <br /> compliance information has not been received resulting in a non-compliant status for this facility. An operator that <br /> receives an inspection report shall have 30 days to submit a written response that includes a statement <br /> documenting corrective actions taken or proposing corrective actions which will be taken. Ensure that a written <br /> response documenting corrective actions taken or proposed is submitted within 30 days of receiving an inspection <br /> report, submit proof of correction to the EHD. <br /> This is a Class II violation. <br /> 123 CCR 2637.1(d), 2637.1(e) Failure to submit the"Spill Container Testing Report Form"within 30 days after the test. <br /> Annual monitoring system certification, leak detector testing, and spill container testing was performed on January <br /> 29, 2018 and a test report was submitted on March 2, 2018, more than 30 days of the test. A copy of the test report <br /> must be submitted within 30 days of the tests. Take all necessary precautions to ensure testing and submittal of <br /> test reports are performed in a timely manner. <br /> This is a Class II violation. <br /> 209 CCR 2716(a-e) Failure to conduct the designated UST operator visual inspection at least once every 30 days. <br /> The designated operator failed to document all the alarms from the attached alarm history on the April 26, 2018 <br /> designated operator monthly inspection report and failed to check that they were responded to appropriately. The <br /> missing alarm includes: Q3 alarm which occurred on April 6, 2018. During the monthly inspection, the designated <br /> operator shall review the alarm history for the previous month, check that each alarm was documented and <br /> responded to appropriately, and attach a copy of the alarm history with documentation taken in response to any <br /> alarms to the monthly report. Ensure that designated operators performing monthly inspections at this facility are <br /> including all of the required information on the reports. <br /> This is a Class II violation. <br /> 304 HSC 25290.1(d) Monitoring system not maintained to detect entry into secondary containment (after Jul 2004). <br /> This is a minor violation. <br /> FA0003635 PR0231656 SCO01 01/22/2019 <br /> EHD 23-01 Rev.09/28/2018 Page 4 of 6 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 952051 T 209 468-3420 1 F 209 464-0138 1 www.sjcehd.com <br />