0 <br />VISUAL INSPECTION OF INTERIOR: No Failure as of July 15 2011 <br />TANK PARAMETERS ON INSPECTION: No leakage Between Walls <br />SECONDARY CONTAINMENT: Double Wall Tank with Dipstick Checked Weekly <br />CONTAINMENT VOLUME 125% of Capacity <br />CONTAINMENT CONDITIONS: Very Good <br />TANK INTEGRITY TEST: A visual inspection of all area of this double wall tank showed no signs of over flow <br />or leakage. No leaks in piping were found under 5 psi pressure. <br />TEST PROCEDURE: All vents and tank outlets where removed and pugged to be air fight for pressure test <br />Air pressure to 5 psi was applied thru a Schroder valve. <br />LEAKS: Air pressure in the tank dropped by .6 lbs. in the first 10 min. of the test. A soap <br />solution was applied to all vent pugs. One vent plug and one extraction cap were found <br />to be leaking. They were both tightened and the leaks stopped. <br />RETURN TANK TO SERVICE: Re -install vents and vacuum extraction outlet and resume use. <br />EQUIPMENT: Plugs, Caps, and a Pressure Gauge to 15 psi <br />TIME PRESSURE TEMP. DEG. F NOTES <br />09:15 AM 0.0 69.0 START SLOW PRESSURE BUILD <br />09:30 AM 5.0 70.0 AIR LEAK AT PLUGS <br />09:45 AM 5.0 70.0 <br />10:00 AM 5.0 70.0 <br />10:15 AM 5.0 70.0 <br />10:30 AM 5.0 71.0 <br />TEST COMPLETED: 10:30 AM 5.0 71.0 <br />NO LEAKS NO TANK FRACTURES <br />TEST COMPLETE <br />PRESSURE ON BOTTOM OF TANK WITH Z OF PRODUCT AND 5.0 PSI AIR PRESSURE 5.75 PSI <br />TANK FILL PIPING AND FEED PUMP <br />All tank piping and used oil pump were tested under 5 psi along with the tank at the same <br />time as the let piping was not capped or plugged. No leaks were found in any of the inlet <br />piping to the tank. <br />OPERATION OF TANK AND EQUIP Acme Truck Parts and Equipment, inc is open for business 40 hours per week. <br />OFF HOURS PROTECTION After hours the site is protected by a 8' chain link fence toped with razor wire and <br />perimeter alarm system. <br />