Laserfiche WebLink
SAN :JOAQUIN Environmental Health Department <br /> COUNTY <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> E F KLUDT&SONS INC 1126 E PINE ST, LODI February 05, 2019 <br /> Item# Remarks <br /> 104 CCR 2711 UST operating permit application for facility and tank information not submitted or current. <br /> UST Tank Information forms for the racing fuel and Kerosene are not current in CERS. Both tanks state to be steel <br /> for primary containment and Jacketed as secondary containment however based on the service technician <br /> statement and observations the tanks have secondary containment to be Steel. Any change of information must be <br /> updated in CERS within 30 days of the changes. Immediately log into CERS, update the required information, and <br /> submit for review by the EHD. <br /> This is a Class II violation. <br /> 201 CCR 2712(b) Failure to maintain monitoring, maintenance, and follow up action records. <br /> Maintenance and monitoring records for the last three years were not found on site. Monitoring system certification <br /> for 2017 were not available for review at the time of inspection. These records shall be maintained on site for at <br /> least three years. Monitoring records include: (1)date and time of all monitoring or sampling; (2)monitoring <br /> equipment calibration and maintenance records; (3)results of any visual observations; (4)results of sample analysis <br /> performed a lab or in the field; (5)logs of all readings of gauges or other monitoring equipment, ground water <br /> elevations, or other test results; (6) results of inventory readings and reconciliations. The operator was able to get <br /> the test results emailed while the inspector was on site to correct the violation with inspector on site. <br /> This was corrected on site. <br /> This is a minor violation. <br /> 209 CCR 2716(a-e) Failure to conduct the designated UST operator visual inspection at least once every 30 days. <br /> In the March 1st, 2018 inspection report the DO failed to print the alarm history for L3-UDC 11/12. <br /> In the June 4th, 2018 inspection report the DO failed to print the alarm history for L4-UDC 13/14. <br /> In the September 4th, 2018 inspection report the DO failed to print the alarm history for L13-Dyed Diesel 1 STP. <br /> In the December 6th, 2018 inspection report the DO failed to print the alarm history for L14-Dyed Diesel 2 STP. <br /> The DO failed to sign the Designated inspection report on 12/6/18, 1/4/19 and 2/1/19. The DO was present at the <br /> time of inspection and was able to sign the reports to correct this part of the violation while the inspector was on site. <br /> During the monthly inspection, the designated operator shall review the alarm history for the previous month, check <br /> that each alarm was documented and responded to appropriately, and attach a copy of the alarm history with <br /> documentation taken in response to any alarms to the monthly report. Ensure that designated operators performing <br /> inspections at least once every 30 days at this facility and are including all of the required information on the reports. <br /> This is a repeat violation, Class II. <br /> 306 CCR 2630(d)Monitoring equipment is not installed or maintained to detect a leak at the earliest opportunity. <br /> Pig mats were observed in UDC SAT 9, UDC 7/8, UDC 9/10, UDC 11/12, and UDC 13/14 preventing the UDC <br /> sensor to detect a leak at the earliest opportunity. Monitoring equipment shall be maintained to be able to detect a <br /> leak at the earliest possible opportunity. The pig mats were removed by the service technician while the inspector <br /> was on site. Ensure that all monitoring equipment is maintained to detect a leak at the earliest opportunity. <br /> This is a Class II violation. <br /> FA0003771 PR0231364 SCO01 02/05/2019 <br /> EHD 23-01 Rev.09/28/2018 Page 4 of 6 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjcehd.com <br />