t <br /> iVICCam ue�� Analytical Inc 110 2nd Avenue South,ND7,Pacheco CA 94553-5560 <br /> p ] Telephone 925-798-1620 Fax 925-798-1622 <br /> hnp//www mccamplxll com E-mail mem ccamphell com <br /> QC SUMMARY REPORT FOR SW8015C <br /> Matrix W Workorder 0303448 <br /> EPA Method SW8015C Extraction SW3510C BatchlD 6328 Spiked Sample ID N/A <br /> Sample Spiked MS* MSD" MS-MSD" LCS LCSD LCS-LCSD Acceptance Criteria(%) <br />' Compound <br /> NgIL Ng/L %Rec %Rec %RPD %Rec %Rec %RPD Low High <br /> TPH(d) N/A 7500 N/A NIA N/A 102 103 1 00 70 130 <br />' %SS N/A 100 N/A N/A NIA 108 109 0 496 707 130 <br /> All target compounds in the Method Blank of this extraction batch were ND less than the method RL with the following exceptions <br />' NONE <br /> li <br /> I <br /> 1 <br /> 1 <br /> 1 <br /> I <br /> I <br /> I MS=Matrix Spike MSD=Matrix Spike Duplicate,LCS=Laboratory Control Sample LCSD=Laboratory Control Sample Duplicate RPD=Relative Percent <br /> Deviation <br /> NIA=not enough sample to perform matrix spike and matrix spike duplicate <br /> NR=analyte concentration In sample exceeds spike amount for soil matrix or exceeds 2x spike amount for water matrix or sample diluted due to high matrix or <br /> anayte content <br /> %Recovery=100'(MS-Sample)/(Amount Spiked) RPD=100"(MS—MSD)/(MS+MSD)`2 <br /> `MS and I or MSD spike recovenes may not be near 100%or the BPDs near 0%if a)the sample is inhomogenous AND contains significant concentrations of <br /> analyte relative to the amount Spiked or b)d that specific sem le metra interferes with spike recov <br />