Laserfiche WebLink
** SPL BATCH QUALITY CONTROL REPORT •* FULLERT0N LABORATORY <br /> 1511E ORANGETHORPE AVE <br /> M8015 - Diesel FULLERTON CA 92631 <br /> PHONE (714)447 6868 <br /> Matrix Water Batch Id GC 6960910015800 <br /> Onits mg/L <br /> L A B O R A T O R Y C O N T R O L S A M P L E <br /> S P I K E Method Spike Blank Spike QC Limits(**) <br /> C O M P O U N D S Blank Result Added Result Recovery (Mandatory) <br /> <2> <3> cl> k k Recovery Range <br /> Petroleum Hydrocarbons-Die ND 20 21 20 106 70 - 140 <br /> M A T R I X S P I K E S <br /> S P I K E Sample Spike Matrix Spike Matrix Spike MS/MSD QC Limits[***) <br /> C O M P O U N D S Results Added Duplicate Relative k (Adviso ) <br /> L Result Recovery Result Recovery Difference RPD <br /> <2> <3> <1> <4> <1> <5> Max Recovery Range <br /> PETROLEUM HYDROCARBONS-DIE ND 20 20 86 104 20 44 102 1 94 20 65 - 135 <br /> Analyst JKA * = Values Outside QC Range <br /> Sequence Date 09/11/96 NC Not Calculated (Sample exceeds spike by factor of 4 or more) <br /> SPL ID of sample spiked 9609046-04A ND x Not Detected/Below Detection Limit <br /> Sample File ID GC6S450 TXO k Recovery = f( <1> - <2> ) / <3> ) x 100 <br /> Method Blank Fxle ID LCS % Recovery - ;<1> / <3> } x 100 <br /> r�Blank Spike File ID GC6B412 TXO Relative Percent Difference = I (<4> - <5> I / [(<4> r <5> 1 x 0 51 x 100 <br /> Matrix Spike File ID GC62413 TXO ;**) = Source <br /> Matrix Spike Duplicate File ID GC6B414 TXO ;***) Source <br /> SAMPLES IN BATCH(SPL ID)_ 9609046-01A 9609046-02A 9609046-03A 9609055-OIB <br /> 9609055-02B 960905S-03B 9609055-04B 9609055-058 <br /> 9609055-06B <br />