Laserfiche WebLink
Reg uirernerrts for Onritinued Service <br /> 2 , 000g Unleaded <br /> o The tank sidewall is only located approx . 9" from the 15, 000 gallon Diesel sidewall . The <br /> rninimum required spacing is calculated using various methods and regulations . Title 8 <br /> § 5590 ( b ) states the sum of the diameters divided by six is the minimum distance the <br /> tanks shall be spaced apart ( approx 28" ) . <br /> o An Emergency Venting device is required on the Annular Space . The spare 4" ports on <br /> the annular space may be adequate to provide this . <br /> o "Safe Filling Level' and "Gasoline" content labels need to be installed on all applicable <br /> portions of the tank . <br /> 15, 000g Diesel <br /> o The tank sidewall is only located approx . 9" from the 2, 000 gallon Diesel sidewall . T he <br /> minimum required spacing is calculated using various methods and regulations . Title 8 <br /> § 5590 ( b ) states the sum of the diameters divided by six is the minimum distance the <br /> tanks shall be spaced apart ( approx 28 " ) . <br /> o An Emergency Venting device is required on the Annular Space . The spare 4" ports on <br /> the annular space may be adequate to provide this . <br /> o "Safe Filling Level' and "Diesel' content labels need to be installed on all applicable <br /> portions of the tank . <br /> P 20,000g Diesel <br /> o An Emergency Venting device is required on the Annular Space . The spare 4" ports on <br /> the annular space may be adequate to provide this . <br /> o "Safe Filling Level' and "Diesel' content labels need to be installed on all applicable <br /> portions of the tank . <br /> Professional Opr aiorr <br /> The subject aboveground storage tank ( s ) at Valley Pacific Petroleum , 22888 Kasson Rd , Tracy, CA <br /> 95304 have been inspected using procedures found in STI SP -001 ( 5th Edition )• publication " Standard for <br /> the Inspection of Aboveground Storage Tanks " . <br /> It is the professional opinion of this firm that the tanks are in acceptable condition , and fit for <br /> continued service ( pending completion of the required repairs ) . <br /> This is not to be construed as an expressed or implied warranty of f uture performance . <br /> Should you have any questions or comments concerning this inspection report, please do not <br /> hesitate to contact the undersigned at 415 -997 ,, 8034 or via email at mitred@NWTLI . com . <br /> Michael Driggs <br /> rniked@NWTLI . com <br /> SP -001 Inspector ( 810125 ) <br />