Laserfiche WebLink
OCT-01-2004 18:3e SERVICE STATION SYSTEM 408 971 0135 P.oe <br /> ANNUAL TEST RESULTS FOR THE PRODUCT AND VAPOR OVERFILL CONTAINMENT <br /> Safeway Date: 9/2/04 <br /> 1804 W.11"'St—Tracy,Ca.95376 <br /> Test Method Developed By: ❑Spill Bucket Manufacturer tai Industry Standard ❑Professional Engineer <br /> ❑Other(Sp(,,cify) <br /> Test Method Used: M Hydrostatic <br /> ❑Other(Specify) <br /> Test Equipment Used_Measuring tape Equipment Resolution: <br /> Exam le- 1/8"increments <br /> Spill Box#87 Spill Box#89 Spill Box#91 Spill Box# <br /> Bucket Capacity in gallons: 5-F 5-V 5-F 5-V 5-F 5-V <br /> Bucket Depth: 12" 12" 12" 12" 12" 12" <br /> Wait time between filling with <br /> water and starting test: <br /> Test Start Time: 9:15 am 9:15 am 9:15 am 9:15 am 9:15 am 9:15 am <br /> initial Reading(Rj): 6`/z'9 6 '/ 6 Y" 7 %" 7" 7" <br /> Test End Ti C: 10:15 am ; 10:15 am 10:15 am 10:15 am 10:15 am 10:15 am <br /> Final Reading(RF): 6 Y2" 6 3/ 6'/2" 7 ,V„ 7" 7" <br /> Test Duration: 1 hour 1 hour 1 hour 1 hour 1 hour 1 hour <br /> Change in Reading(RF-RI): None None None None None None <br /> Pass/Fail Threshold or Criteria: "ZERO LOSS ZERO LOSS ZERO LOSS <br /> q y� �Cp 9 v�e <br /> t.i 1 <br /> ON <br /> �^'>a F�711.a< � d1e' m � Ns � <br /> 00 <br /> Comments—(include inj6matian on repairs made prior to testing, and recommended follow-up for failed tests) <br /> All Buckets Passed. <br /> Tested By: Service Station Systems, Inc. Technician: Tim Riddle <br /> Contractor License: 485184 <br /> TOTAL P.08 <br />