Laserfiche WebLink
Site Tested <br />GilbNR Testing <br />Safeway <br />1804 West 11 Th. Street <br />Tracy, CA 95376 - <br />Product and Vapor Overfill Containment <br />Test Results <br />Test performed by <br />Serv. Sta. Sys. <br />680 Quinn Ave. <br />San Jose CA 95112 <br />License #: 485184 <br />Tech: Bryan Lundien <br />Test Date: 8/3/09 <br />Test Method Developed By: ❑ Spill Bucket Manufacturer ® Industry Standard ❑ Professional Engineer ❑ Other(Specify) Test Method Used: ® Hydrostatic ❑ Olher(Specity) <br />Test Equipment Used:Measuring Tape Equipment Resolution:)/16 in. Example - 1/8" increments Pass/Fail Threshold or Criteria: Zero Loss <br />Comments: Tank 1 -87: found bad o -ring, replaced and re -tested. Passed <br />Product Fill Bucket <br />Vapor Fill Bucket <br />Tank /Grade <br />wait <br />(min) <br />Start <br />Time <br />Stop (hrs.) <br />Gel. <br />Depth <br />Pass <br />Initial - Final = Change /Fail <br />Gal. <br />Depth <br />Initial - Final = Change <br />Pass <br />/Fall <br />01 - Regu <br />5 <br />3:20pm <br />4:20pm 1.0 <br />; 5 <br />13.50 <br />13.50 - 13.50 = 0.00 Pass <br />02 - Plus <br />5 <br />1:30pm <br />2:30pm 1.0 <br />5 <br />12.75 <br />12.76 - 12.75 = 0.00 Pass <br />03 - Prem <br />5 <br />1:30pm <br />2:30pm 1.0 17-97 <br />1 <br />13.13 <br />13.13 -13.13 = 0.00 Pass <br />Comments: Tank 1 -87: found bad o -ring, replaced and re -tested. Passed <br />