Laserfiche WebLink
8. FILL RISER CONTAINMENT SUMP TESTING <br />Facility is Not Equipped With Fill Riser Containment Sumps ❑ <br />Fill Riser Containment Sumps are Present, but were Not Tested ❑ <br />Test Method Developed By: ❑ Sump Manufacturer ® Industry Standard ❑ Professional Engineer <br />❑ Other (Specify) <br />Test Method Used: ❑ Pressure ❑ Vacuum ® Hydrostatic <br />❑ Other (Spec) <br />Test Equipment Used: Incon Sump Tester Equipment Resolution: +/- 0.002" <br />Fill Sump # Diesel <br />Sump Diameter: 48" <br />Sump Depth: 60" <br />Height from Tank Top to Top of 36" <br />Highest Piping Penetration: <br />Height from Tank Top to Lowest 19" <br />Electrical Penetration: <br />Condition of sump prior to Good <br />testing: <br />Portion of Sump Tested 2" above piping <br />Sump Material: Fiberglass <br />Wait time between applying <br />pressure/vacuum/water and 30 minutes <br />starting test: <br />Test Start Time: 9:06 am <br />Initial Reading (R,): 3.3896 <br />Test End Time: 9:21 am <br />Final Reading (RF): 3.3910 <br />Test Duration: 15 min. <br />Change in Reading (117111): +0.0014 <br />Pass/Fail Threshold or Criteria: +/- 0.002" <br />Test Result: © Pass ❑ Fail <br />Is there a sensor in the sump? ® Yes ❑ No <br />Does the sensor alarm when <br />either product or water is ❑ Yes ❑ No ® NA <br />detected? <br />Was sensor removed for testing? ® Yes ❑ No ❑ NA <br />Was sensor properly replaced and ® Yes ❑ No ❑ NA <br />verified functional after testing? <br />Comments — (include information on repairs made prior to testing, and recommended follow-up for jailed tests) <br />"Sensor functionality was not confirmed. This procedure is not part of the Secondary Containment testing scope of work". <br />