Laserfiche WebLink
14. SECONDARY PIPE TESTING <br />Test Method Developed By: ❑ Piping Manufacturer ® Industry Standard ❑ Professional Engineer <br />❑ Other (Spec) <br />Test Method Used: ® Pressure ❑ Vacuum ❑ Hydrostatic <br />❑ Other (Spec) <br />Test Equipment Used: Test reducer boots, Nitrogen and gauges Equipment Resolution: 0.5% of span <br />Piping Run # 87 —S Piping Run # 91 -S Piping Run # Diesel —S <br />Piping Material: Coflex Coflex Coflex <br />Piping Manufacturer: <br />Western Fiberglass <br />Western Fiberglass <br />Western Fiberglass <br />Piping Diameter: <br />2" <br />1 'h" <br />Length of Piping Run: <br />Product Stored: <br />Gasoline <br />Gasoline <br />Diesel <br />Method and location of <br />-piping-run isolation: <br />Reducer Boots/Fittings <br />Reducer Boots/Fittings <br />Reducer Boots/Fittings <br />Wait time between applying <br />pressure/vacuum/water and <br />starting test: <br />10 minutes <br />10 minutes <br />10 minutes <br />Test Start Time: <br />12:50 pm <br />12:50 pm <br />10:20 am <br />Initial Reading (R1): <br />5 psi <br />5 psi <br />5 psi <br />Test End Time: <br />1:50 pm <br />1:50 pm <br />11:20 am <br />Final Reading (RF): <br />5 psi <br />5 psi <br />5 psi <br />Test Duration: <br />1 hr. <br />1 hr. <br />1 hr. <br />Change in Reading (RF-Ri): <br />none <br />none <br />none <br />Pass/Fail Threshold or <br />Criteria: <br />No detectable Loss <br />No detectable Loss <br />No detectable Loss <br />Test Result: <br />O Pass 0 Fait <br />I El Pass 0 Fail <br />© Pass 0 Fail <br />Comments — (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />UDC 3/4 — replaced a 20x20 test boot (diesel) <br />UDC 7/8 — replaced a 20x20 test boot (2 diesel) and 3 jumpers — also replaced 20x2OA test boot on #7 side (diesel) <br />UDC 11/12 — replaced a 20x20 test boot (2 diesel) and 3 jumpers — also tightened clamps <br />UDC 15/16 — replaced all 4 20x20 test boots, 2 2.5x2.5A test boots (2 87, 91 and Diesel) and 3 jumpers — also tightened clamps <br />UDC 19/20 — replaced all 4 20x20 test boots, 2 2.5x2.5A test boots (2 87, 91 and Diesel) and 3 jumpers <br />* 87-S and 91-S was tested on 4/1 /10 <br />*Diesel -S was tested on 4/7/10 <br />