Laserfiche WebLink
6. PIPING SUMP TESTING <br />Test Method Developed By: ❑ Sump Manufacturer Industry Standard ❑ Professional Engineer <br />❑ Other (Spec) <br />Test Method Used: ❑Pressure ❑ Vacuum Hydrostatic <br />❑ Other (Spec) <br />Test Equipment Used: Incon Sump Tester <br />Sump # 87 Sump # 91 <br />Equipment Resolution: +/- 0.002 Inches <br />Sump # Diesel <br />7sump # <br />Sump Diameter: <br />42" <br />42" <br />42" <br />Sump Depth: <br />72" <br />73" <br />73" <br />Sump Material: <br />Fiberglass <br />Fiberglass <br />Fiberglass <br />Height from Tank Top to Top of <br />Highest Piping Penetration: <br />12" <br />12" <br />12" <br />Height from Tank Top to Lowest <br />Electrical Penetration: <br />14" <br />13" <br />13" <br />Condition of sump prior to testing: <br />Good <br />Good <br />Good <br />Portion of Sump Tested` <br />2" Above Piping <br />2" Above Piping <br />2" Above piping <br />Does turbine shut down when <br />sump sensor detects liquid (both <br />product and water)?* <br />❑Yes ❑No [DNA <br />Dyes ❑No [DNA <br />[:]yes[:] No ❑✓ NA <br />❑ Yes ao ❑NA <br />Turbine shutdown response time <br />N/A <br />N/A <br />N/A <br />N/A <br />Is system programmed for fail-safe <br />shutdown?* <br />Dyes ❑No ❑NA ❑Yes ❑No [DNA []Yes[-] No [DNA ❑ Yes DNA <br />Was fail-safe verified to be <br />operational?* <br />❑1'es ❑No [Z]NA <br />[-]Yes[-]No❑✓ NA <br />❑Yes ❑No ✓❑NA <br />❑Yes ❑No ❑NA <br />Wait time between applying <br />pressure/vacuum/water and starting <br />test: <br />30 Minutes <br />30 Minutes <br />30 Minutes <br />30 Minutes <br />Test Start Time: <br />1:55PM <br />11:49AM <br />1:05PM <br />Initial Reading (RI): <br />5.1162 Inches <br />2.5182 Inches <br />2.9917 Inches <br />Inches <br />Test End Time. <br />2:10PM <br />12:04PM <br />1:20PM <br />Final Reading (RF): <br />5.1146 Inches <br />2.5180 Inches <br />2.9905 Inches <br />Inches <br />Test Duration: <br />15 Minutes <br />15 Minutes <br />15 Minutes <br />Change in Reading (RF -RI): <br />0.0016 <br />0.0002 <br />0.0012 <br />Pass/Fail Threshold or Criteria: <br />0.002 <br />0.002 <br />0.002 <br />0.002 <br />Test Result: <br />❑✓ Pass ❑Fail <br />[2]Pass ❑Fail <br />✓❑Pass ❑Fail <br />❑Pass ❑Fail <br />Was sensor removed for testing? <br />Dyes ❑No DNA <br />Eyes ❑No ❑NA <br />❑✓ Yes ❑No DNA <br />❑ Yes ❑No DNA <br />Was sensor properly replaced and <br />verified functional after testing? <br />❑yes ❑No DNA <br />❑✓ Yes ❑No DNA <br />[D Yes ❑No DNA <br />❑ Yes ❑No ❑NA <br />Comments —(include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />Diesel STP sump torn test boot, replaced boot, retest and passed. <br />"Sensor functionality was not confirmed. This procedure is not part of the Secondary Containment <br />testing scope of work". <br />