Laserfiche WebLink
POWERS Pa7OA7 � <br /> evaan,cnetstn STI SP-001 INSPECTION <br /> TFVO]]N GEORGE REED NC MODESTO,CA <br /> FPII]0]832 YIBi <br /> ENSNEERINS&INSPECTION,INC. SS-1 <br /> 3. Ultrasonic Thickness Test <br /> Ultrasonic Thickness Testing was performed on accessible sections of the steel tank shell and end caps. <br /> All spot readings returned nominal thickness, approximately 0.190-in. All UT scrubs had minimal to no <br /> change in signal signifying little to no metal loss. Any variations or changes in thickness outside of the <br /> original nominal thickness (if any)would be documented and analyzed in this section. Access to the third <br /> coursewas not possible during the inspection. <br /> Shell Course Thickness(in.) <br /> 1 0.190 <br /> 2 0.190 <br /> 3 No Access <br /> ..19F�f1B}y�rg19d3]x8e CaePnMQ V W1P <br /> OID1P£Llrc <br /> Page 14 <br />