Laserfiche WebLink
McLane Att <br /> 800 Mellon Avenue McLANE <br /> Manteca, CA 95337 <br /> #2 Diesel Fuel Tank <br /> Secondary Tank Test Parameters <br /> Certified UL 2085 <br /> 250 Gallons Time Pressure AP #2 Diesel fuel tank <br /> Fireguard 0 3.0 psi 0 250 gallons. <br /> UL 2085 5 3.0 psi 0 Pneumatic pressure <br /> #10213 10 3.0 psi 0 was used to certify <br /> 15 3.0 psi 0 the secondary <br /> 20 3.0 psi 0 containment space. <br /> System was <br /> 25 3.0 psi 0 pressurized to 3.0 <br /> 30 3.0 psi 1 0 psi and held for 60 <br /> 35 3.0 psi 0 minutes with no <br /> 40 3.0 psi 0 loss in pressure. <br /> 45 3.0 psi 0 <br /> 50 3.0 psi 0 <br /> 55 3.0 psi 0 <br /> 60 3.0 psi 0 <br /> SP001 certification testing was performed on April 16, 2019, at McLane located at <br /> 800 Mellon Avenue, Manteca, CA 95337. Testing was performed to Industry <br /> Standards on the 250 Gallon#2 Diesel Fuel tank and the secondary space tank was <br /> tested to 3.0 psi. The tank passed its Industry Standards certification testing. No <br /> defects were observed and the#2 Diesel Fuel system was observed to be in <br /> compliance with Industrial Standards testing requirements. <br /> Test Device: Ashcroft T5500 SS 0-5 psi Pressure Gauge_ <br /> Test Gas:_Nitrogen Gas_ <br /> Test Pressure: _3.0 psi_ <br /> Test Duration: 60 minutes <br /> Tank Capacity: _250Gallons_ %- - - <br /> Tank Volumne 210 Gallons_ <br /> Certified Tester:_Gary Reeves_ <br /> xe c * S.Cl2 T <br /> REA#30349 <br /> ICC#8019664 All <br /> SP001 Level II #11111 <br /> NDT-UT Level 111 #001 <br />