Laserfiche WebLink
SSA <br /> II`,,JRSAnalysIS <br /> A.4BC <br /> 1 • I i • <br /> Date 4-Aug-16 Flood KH-1 Unit I KH-1 <br /> Exhaust Section <br /> Manufacturer Captiveaire Model 6024 VHB <br /> Serial Number DNL Location Kitchen A10 <br /> Measurements <br /> 1 2 3 4 5 6 7 8 9 10 11 <br /> A 937 <br /> B <br /> C <br /> D <br /> Size of Opening 1 18 (1 n.) X 14 (In.) 252 1144 = t 1.75 1 SQFT <br /> Total FPM - No. of Readings = Avg. FPM X Area = Total CFM <br /> 937 1 937 1.750 1,640 <br /> Filter Data <br /> Filter Size - Manufacturer - <br /> Avg.Velocity - Filter Area - <br /> Filter Factor - ;; CFM - <br /> Supply Section Measurements <br /> 1 2 3 4 56 7 8 9 10 11 <br /> A 284 <br /> B <br /> C <br /> D <br /> Size of Opening 46 (In.) X 1 16 (In.) _ 1 736 1144 = ! 5.111111111 SQFT <br /> Total FPM No.of Readings = Avg. FPM X Area X K Factor - Total CFM <br /> 284 1 2845.111 1 1,452 <br /> Test Data <br /> Design Data Test Data <br /> Exhaust CFM 1600 1,640 <br /> Make-Up CFM 1440 1,452 <br /> Percentage 90% 89% <br /> Remarks (1)Velocity shown for the make-up air is only shown for percentage comparison only. Actual testing was <br /> erfromed with a flow hood and not via traverse. Refer to MUA-1 fan test sheet along with the associated grille and diffuser <br /> test sheet for actual tested data. <br /> 2 Theopening of the kitchen hood is not 18" by 14". It is a 18" round duct measured with an airfoil. Again, <br /> measurements were entered on this form for percentage comparison purposes only. Refer to KEF-1 fan test page and the <br /> associated grille and diffuser test sheet for actul tested data. <br />