Laserfiche WebLink
SWRCB, January 2002 Page z-9 of <br />4. TANK ANNULAR TESTING <br />Test Method Developed By: X Tank Manufacturer ❑ Industry Standard ❑ Professional Engineer <br />❑ Other (Spec) <br />Test Method Used: ❑ Pressure X Vacuum 0 Hydrostatic <br />❑ Other (Sped) <br />Test Equipment Used: Gast Vacuum Pump/Vacuum Gauges in Fig. <br />Equipment Resolution: -0/-30 Fig. <br />Is Tank Exempt From Testing?' <br />Tank # 1 <br />Yes x No <br />Tank # 2 <br />Yes x No <br />Tank # 3 <br />Yes x No <br />Tank # <br />❑ Yes ❑ No <br />Tank Capacity: <br />12K <br />12K <br />12K <br />Tank Material: <br />Fiberglass <br />Fiberglass <br />Fiberglass <br />Tank Manufacturer: <br />Owens Corning <br />Owens Corning <br />Owens Corning <br />Product Stored: <br />Regular 87 Master <br />Regular 87 Slave <br />Premium 91 <br />Wait time between applying <br />vacuum and starting test: <br />1 Hour <br />I Hour <br />I Hour <br />Test Start Time: <br />11:15 <br />11:25 <br />11:35 <br />Initial Reading (Rj): <br />-10 Hg. <br />-10 Hg. <br />-10 Hg. <br />Test End Time: <br />12:15 <br />12:25 <br />12:35 <br />Final Reading (RF): <br />-10 Hg. <br />-10 Hg. <br />-10 Hg. <br />Test Duration: <br />1 Hour <br />1 Hour <br />1 Hour <br />Change in Reading (RF-Rj): <br />0 <br />0 <br />0 <br />Pass/Fail Threshold or Criteria: <br />➢ -2 Hg. <br />➢ -2 Hg. <br />➢ -2 Fig. <br />Test Result: <br />X Pass ❑ Fail <br />X Pass ❑ Fail <br />X Pass ❑ Fail <br />❑ Pass ❑ Fail <br />Was sensor removed for testing? <br />Yes X No ❑ NA <br />Yes X No ❑ NA <br />Yes X No 0 NA <br />❑ Yes ❑ No ❑ NA <br />Was sensor properly replaced and <br />verified functional after testing? <br />Yes ❑ No X NA <br />Yes 0 No X NA <br />Yes 0 No X NA <br />❑ Yes 0 No ❑ NA <br />Comments — (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />' Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary <br />containment, such as systems that are hydrostatically monitored or under constant vacuum, are exempt from periodic containment <br />testing. {California Code of Regulations, Title 23, Section 2637(a)(6)) <br />