Laserfiche WebLink
SWRCB,January 2002 Page of <br /> 9. FILL RISER CONTAINMENT SUMP TESTING <br /> Facility is Not Equipped With Fill Riser Containment Sums ❑ <br /> Fill Riser Containment Sumps are Present,but were Not Tested ❑ <br /> Test Method Developed By: 11 Sump Manufacturer ❑Industry Standard X Professional Engineer <br /> ❑Other(Specify) <br /> Test Method Used: ❑Pressure ❑Vacuum X Hydrostatic <br /> ❑Other(Specify) <br /> Test Equipment Used: Caldwell Level Change Indicator Equipment Resolution .002 <br /> Fill Sump# I-87-NI Fill Sump#2-87-S FW Sump#3-91 Fill Sump# <br /> Sump Diameter: <br /> 42" 42" 42" <br /> Sump Depth: 46" 53" 48" <br /> Height from Tank Top to Top of 22" 23" 22" <br /> Highest Piping Penetration: <br /> 20" <br /> Height from Tank Top to Lowest 20" 24" <br /> Electrical Penetration: <br /> Condition of sump prior to Dry Dry Dry <br /> testis <br /> Portion of Sump Tested Water Level 24'/2" Water Level 26" Water Level 24" <br /> Sump Material: Fiberglass Fiberglass Fiber lass <br /> Wait time between applying 5 Minutes 5 Minutes 5 Minutes <br /> water and starting test: <br /> Test Start Time: 12:07 12:52 1:37 <br /> Initial Reading ► : .001 .001 .001 <br /> Test End Time: 12:37 1:22 2:07 <br /> Final Reading(RF): .001 .001 .001 <br /> Test Duration: 30 Minutes 30 Minutes 30 Minutes <br /> Change in Reading (RF—R,): 0 0 0 <br /> Pass/Fail Threshold or Criteria: .005/30 Minutes .005/30 Minutes .005/30 Minutes <br /> Test Result: Pass Pass Pass <br /> Is there a sensor in the sump? Yes Yes Yes <br /> Does the sensor alarm when <br /> either product or water is Yes Yes Yes <br /> detected? <br /> Was sensor removed for testis ? Yes Yes Yes <br /> Was sensor properly replaced and Yes Yes Yes <br /> verified functional after testing? <br /> Comments—(include information on repairs made prior to testing,and recommended follow-up for.failed tests) <br />