Laserfiche WebLink
Triangle Environmental, Inc. <br /> T.E.I. SYSTEMS TANK, LINE AND LEAK DETECTOR TEST REPORT <br /> Facility: ARCO #02186 <br /> Tank #: 2 Test Date: 12/22/97 <br /> Product: Unleaded Regular Work#: 50605 <br /> Test Method: System 4000 Test Method: R.J. FTA <br /> Capacity: 9728 Manufacturer: Vaporless <br /> Diameter(in): 92 L/D Model: LD2000 <br /> Product Level(in): 63 L/D Serial#: 67425-- <br /> Liquid Volume(Gals): 7129 Line Drain Back(ml): 190 <br /> Liquid Percent(%): 73.3% L/D Trip Time(sec): 2 <br /> Specific Gravity: 0.750 Holding Pressure(psi): 27 <br /> Coef.of Expansion: 0.000655 Metering Pressure(psi): 13 <br /> Water On Tank(in): 0 L/D Test Rate(gph): 1.0 <br /> Water In Tank(in): 0 L/D Result: PASS <br /> Product Temp. (F): 61.055 <br /> Head Pressure(psi): 1.7 <br /> Test Start Time: 1:00:00 PM Test Method: TEI LT-3 <br /> Test End Time: 3:30:00 PM Pump Brand: Red Jacket <br /> Test Rate(gph): -0.027 System Type: Pressure <br /> Test Result: PASS Line Pressure(psi): 50 <br /> Line Start Time: 1:45:00 PM <br /> Test Method: ULLAGE Line End Time: 2:00:00 PM <br /> UllageVolume(gals.): 2599 Line Start Level: 100 <br /> Ullage Test Time: 4:04:00 PM Line End Level: 79 <br /> Ullage Vacuum(psi): 2 Line Test Rate(gph): -0.021 <br /> Ullage Result: PASS Line Test Result: PASS <br /> 3 <br />